PSBEN10A12C  

 

 

 
 

12 

4.2. Deep discharge battery protection UVP. 

The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at 

the battery terminals drops below10V±0.2V during battery-assisted operation, the PSU will be disconnected within 
approx. 15s. The protection mode is off when the P

BAT 

jumper is removed. 

 
 

Caution. 
Deactivating of the UVP function  is not recommended since a deep discharge of the battery  limits its 
capability of storing energy, lowers its capacity and shortens its durability. 

 
 

4.3 Dynamic battery test. 

The PSU runs a battery test every  10 minutes. It is done by a momentary switching into a battery-assisted 

operation. A failure is indicated when voltage drops below 12V. The battery test facility can be switched off. 

 

Deactivating/activating  the  test:  during  mains-powered  PSU  operation  press  the  STOP  button  on  the 

main  board  and  hold  it  for  3  seconds.  The  device  will  confirm  the  activation/deactivation  in  the  following  ways: 
(Tab.4, [6], [7]).  

 

testing off – the tOF sign appears on the display 

 

testing on –  the tON sign appears on the display 

 

 
Deactivating/activating  the  test  is  stored  in  the  memory  even  after  unplugging  the  device  from 
mains.  The  battery  failure  indication  at  the  APS  FLT  output  is  automatically  switched  off.  The 
battery protection system against deep discharged remains on, though. 
 

 
            4.4. Standby time.  
The  standby  time  during  batter-assisted  operation  depends  on:  battery  capacity,  battery  charge  level  and 

load current. In order to keep the standby time, the current drawn from the PSU during battery-assisted operation 
should be limited. Characteristics for a 17Ah/12V SLA: 

 
Grade 1, 2 - standby time 12h   

 

 

 

 

Output current 1,4A + 3A battery charge 

 
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving 
Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,56A + 3A battery charge 

 

 
 - standby time 60h if the faults of the main power source are reported to the Alarm Receiving 

Centre - ARC (in accordance with 9.2 – PN-EN 50131-1). 
 

 

 

Output current 0,28A + 3A battery charge 

 
 
 

4.5. Battery charging time. 

 

The  PSU  has  a  battery  circuit  charged  with  direct  current.  The  current  selection  is  done  via 

I

BAT

  jumpers. 

The  table  below  shows  how  long  it  takes  to  charge  a  (fully  discharged)  battery  up  to  min.  80%  of  its  nominal 
capacity.  

Table 5. Battery charging time. 

17Ah

 battery charging time  

up to capacity of 0,8*C 

Charging 

current [A] 

Configuration of 

I

BAT 

jumper 

5h6m 

J1= 

, J2= 

, J3= 

 

7h 

2,2 

J1= 

, J2= 

  J3= 

 

10h12m 

1,5 

J1= 

, J2= 

  J3= 

 

25h30m 

0,6 

J1= 

, J2= 

  J3= 

 

 

 
 
 
 
 
 
 

Summary of Contents for BLACK POWER PSBEN 10A12C

Page 1: ...PSBEN 10A12C v 1 0 PSBEN 13 8V 10A 17Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Page 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 13 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Page 3: ...indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technic...

Page 4: ...rce are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN...

Page 5: ...T button launching the PSU from a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper...

Page 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Page 7: ...pproving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presenc...

Page 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Page 9: ...r 9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displaye...

Page 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Page 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Page 12: ...after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though 4 4 S...

Page 13: ...uration of jumpers In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without bat...

Page 14: ...es 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequen...

Page 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Page 16: ...on with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo r...

Page 17: ...eneral use Io 10A 0 6A battery charge Io 9 1A 1 5A battery charge Io 8 4A 2 2A battery charge Io 7 6A 3A battery charge Output voltage setting escalation and keeping time 8ms 3ms 25ms Output voltage a...

Page 18: ...e Connectors Supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 M6 0 2 5 56cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can b...

Page 19: ...ntees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Co...

Page 20: ...s to protect the battery and the receivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status...

Page 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Reviews: