Pulsar BLACK POWER PSBEN 10A12C Manual Download Page 18

www.pulsar.pl   

 

 

 

PSBEN10A12C  

 

 

 
 

18 

EXT IN technical input 

Voltage ’on’ –  10÷30V DC 
Voltage ’off’ –  0÷2V DC 
Level of galvanic isolation: 1500V

RMS

 

Optical indication: 

- LEDs on the PSU’s pcb, 
- LED panel 

  output current readings 

  output voltage readings 

 

failure codes with history

 

Acoustic indication: 

- piezoelectric indicator ~75dB /0,3m, switchable via jumper

 

F

BAT 

fuse

 

F

MAIN 

fuse 

T 10A / 250V 
T 6,3A / 250V

 

Additional accessories (not included) 

- interface USB-TTL ‘INTU’; communication: USB-TTL 
- interface RS485 ‘INTR’; communication: RS485 
- interface USB-RS485 ‘INTUR’; communication: USB-RS485 
- interface Ethernet ‘INTE’; communication: Ethernet 
- interface WiFi “INTW’; wireless communication: Wi-Fi 
- interface RS485-Ethernet “INTRE’; communication: RS485-      
Ethernet 
- interface RS485-WiFi “INTRW’; wireless communication: 
RS485-WiFi 
 

 

 

Table 7. Mechanical specifications.                                                                                                                              

Enclosure dimensions 

330 x 350 x 108  (335 x 355 x 100+8) (WxHxD) [mm] (+/- 2) 

Fixing 

300x 318 x 

Φ

 6 x4 (WxH) 

Fitting battery 

17Ah/12V (SLA) max. 

Net/gross weight 

6,6/7,1kg 

Enclosure  

Steel plate DC01  1mm, colour RAL 9005 (black) 

Closing 

Cheese head screw x2 (at the front), lock assembly possible 

Connectors 

Supply: 

Φ

0,51÷2 (AWG 24-12) 

Outputs : 

Ф

0,51÷2 (AWG 24-12), battery outputs  BAT: 

Ф

6 (M6-0-2,5) 56cm 

TAMPER output: wires, 25cm 

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 
Convectional cooling. 

 

Table 8. Operation safety. 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

 
Table 9. Operating specifications. 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

Table 10. PSU’s factory settings. 

Indication time of EPS network loss  

5s 

Battery charging current 

3A 

Battery presence 

YES (battery present) 

Battery test 

YES (activated) 

Deep discharge battery protection UVP 

YES (battery protected) 

Communication address  

Transmission 

19.2k 8E1 

Summary of Contents for BLACK POWER PSBEN 10A12C

Page 1: ...PSBEN 10A12C v 1 0 PSBEN 13 8V 10A 17Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Page 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 13 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Page 3: ...indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technic...

Page 4: ...rce are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN...

Page 5: ...T button launching the PSU from a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper...

Page 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Page 7: ...pproving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presenc...

Page 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Page 9: ...r 9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displaye...

Page 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Page 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Page 12: ...after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though 4 4 S...

Page 13: ...uration of jumpers In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without bat...

Page 14: ...es 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequen...

Page 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Page 16: ...on with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo r...

Page 17: ...eneral use Io 10A 0 6A battery charge Io 9 1A 1 5A battery charge Io 8 4A 2 2A battery charge Io 7 6A 3A battery charge Output voltage setting escalation and keeping time 8ms 3ms 25ms Output voltage a...

Page 18: ...e Connectors Supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 M6 0 2 5 56cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can b...

Page 19: ...ntees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Co...

Page 20: ...s to protect the battery and the receivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status...

Page 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...