72-910-16 Rev. N
Page 29 of 43
Skip
– Choose this option if you want the inhibitor to skip a feed cycle if a biocide
happens to be feeding.
Pause
– Choose this option if you want the inhibitor feed cycle to pause or delay until
the biocide feed cycle is complete. When the biocide feed cycle is complete the inhibitor
will then feed.
None
– Choose this option if you want the inhibitor to feed regardless of what the
biocide feed cycles are doing.
Any inhibitor feed time that was paused or skipped due to a biocide feed cycle will not be
added to the next inhibitor feed cycle.
7.26 Biocide A or B Menu
From this menu configure how often and the duration you want the biocide to feed. This
controller can also perform a pre-bleed, using a conductivity minimum and a fixed time, and
bleed-lockout function with each biocide feed.
Days/Weeks
– Set the days and weeks you want the biocide to feed. See the next
section for details on how to set the days and weeks.
Start Times
– Set up to four start times. Setting the value to 00:00 means the start time
is ignored.
Feed Time
– Set this value to the amount of time you want the biocide to feed each time
a feed cycle is started.
Pre-Bleed
– Set the pre-bleed time to the maximum amount of time you want the pre-
bleed function to force a bleed cycle without reaching the conductivity minimum. Set the
conductivity minimum to the value you want the conductivity to reach before the bleed
cycle finishes and the biocide is feed.
Bleed Lockout
– Set this value to the amount of time you want to lock-out a bleed
function after a biocide feed cycle has started.
Home Screen
Settings
Biocide A or B
Days/Weeks
Start Times
Feed Time
Pre-Bleed
Bleed Lkout