Pump Stops
– Selecting this mode causes the inhibitor, biocide A, or biocide B outputs
to de-energize when their drum level goes low.
Pump Runs
– Selecting this mode causes the inhibitor, biocide A, and biocide B outputs
to remain energized even though their drum level has gone low.
When a drum level goes low the controller will go into alarm regardless of this setting.
Re-filling a low drum may cause the pump control output to energize without warning.
7.12 Display Dampener
From the Display Dampener setting option you select how often you want the actual conductivity
reading updated on the Home Screen and dampening of the controller response to sudden
changes in conductivity.
Display Dampener
– Set this value to the number of seconds you want the controller to
dampen the displayed conductivity and controller response.
The controller takes a conductivity reading every second. Increasing this value above one second
causes the controller to average the readings, hence, slowing down the control functions.
7.13 Rising/Falling Setpoint Option
From the Rise/Fall setpoint option you select which direction the conductivity will tend to go in
the process being controlled. If the Microvision is controlling a cooling tower use the Rising
setpoint option.
Home Screen
Configure
Disp Damp
Display
Dampener
01 sec
Cancel |Enter
Home Screen
Configure
Drum Levels
Pump Stops
Pump Runs
Back | Select