QT40.241-B2 Installation Manual
IO-Link Description
Parameter
User specific marking
(Byte)
Output voltage setpoint
(V)
Stress level
(%)
Remaining life time
(%)
Temperature airflow
(°C)
Max. temperature airflow
(°C)
Temperature primary inside
(°C)
Max. temperature primary inside
(°C)
Operating time
(hours)
Operating time
(minutes)
Transient counter overall
Transient counter last 2 minutes
Actual input voltage
(V)
Actual output voltage
(V)
Turn-on counter
Uptime since last turn-on
(hours)
Uptime since last turn-on
(minutes)
EEPROM Status
Shut down
Acyclic Data (Parameters)
Min / Max
0 / 32
15.0 / 28.5
0 / 100
100 / 0
-45 / +150
-45 / +150
-45 / +150
-45 / +150
0 / 262800
0 / 59
0 / 7200000
0 / 7200000
0 / 1130
0 / 40
0 / 7200000
0 / 1000000
0 / 59
0 / 1
0 / 1
Description
User specific number or text
Adjustment value, preset to 24.1V
Average value of last 2 minutes
Estimated value
Income air temperature
Recorded max. temp. since turn on
Component temp. primary side
Recorded max. temp. since turn on
Comulated overall time
Comulated overall time
-
-
RMS value
-
Comulated number of turn-on
-
-
A logic "1" indicates EEPROM ok
A logic "1" turns output off
Notification
DC-OK
DC-Warning
Bonus-Power
Over temperature (capacitors)
Over temperature (airflow)
Overload
High voltage on input
Low voltage on input
Power supply down
Predictive maintenance recommend.
2-Phase operation
Humidity
Events
Min/Max
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
Description
Indicates an output voltage >90% of the
adjusted value
Indicates an output voltage <90% of the
adjusted value
Output current >105% for longer than 3s
Temperature of capacitors >95°C
Inside air temperature (bottom) >65°C
Device operates in current limiting mode
Input voltage above the specified value
Input voltage below the specified value
A logic "1" indicates a power supply failure
Operating hours exceeded the lifetime hours
Indicates a missing leg of the 3-phase
system, see datasheet for more information
Humidity too high or water contamination
Cyclic Data (Process)
Parameter
Output current
(A)
Min/Max
0 / 80
Period
2ms
Description
-
IO Link Connector – Pin Assignment
Pin 1: Supply voltage (+)
Pin 2: Not connected
Pin 3: Supply voltage (-)
Pin 4: Data IN/OUT
1
4
3
2
View from the outside to the power supply