22.5.

 

S

ERIES 

O

PERATION

 

Power supplies of the same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 

with a potential above 60Vdc are not SELV any more and can be dangerous. 
Such voltages must be installed with a protection against touching.  
Earthing of the output is required when the sum of the output voltage is 
above 60Vdc. 
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals.  
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other. 
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
 

22.6.

 

I

NDUCTIVE AND 

C

APACITIVE 

L

OADS

 

The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, 
such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 1.5F are connected to the 
output, the unit might charge the capacitor in the Hiccup

PLUS

 mode (see chapter 6). 

22.7.

 

C

HARGING OF 

B

ATTERIES

 

Do not use the power supply to charge batteries. 
 

22.8.

 

O

PERATION ON 

T

WO 

P

HASES

 

The power supply can also be used on two-phases of a three-phase-
system. Such a phase-to-phase connection is allowed as long as the 
supplying voltage is below 240V

+10%

 
 

22.9.

 

U

SE IN A 

T

IGHTLY 

S

EALED 

E

NCLOSURE

 

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher 
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. 
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. 
The power supply is placed in the middle of the box; no other heat producing items are inside the box. 
Enclosure: 

 

 

Rittal Type IP66 Box PK 9519 100, plastic, 180x180x165mm 

Input:   

 

 

230Vac 

 
Load:    

 

 

24V, 16A; (=80%) load is placed outside the box 

Temperature inside the box:  

51.5°C  (in the middle of the right side of the power supply with a distance of 1cm) 

Temperature outside the box:  

25.5°C 

Temperature rise: 

 

26.0K 

Unit A

AC

DC

Unit B

AC

DC

-

+

-

+

Load

+

-

Earth
(see notes)

240V

 

+10

%

 m

ax.

Fuse

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

Summary of Contents for PIANO Series

Page 1: ...tiple mains inputs the reduction to a regional input voltage range AC 200 240V simplifies the circuitry and has significant advantages for reliability efficiency and cost The addition of a DC OK signa...

Page 2: ...is document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sense of the...

Page 3: ...t by following all local and national codes Use appropriate copper cables that are designed for a minimum operating temperature of 60 C for ambient temperatures up to 45 C 75 C for ambient temperature...

Page 4: ...99 at 24V 20A 230Vac see Fig 3 4 Crest factor typ 1 6 at 24V 20A 230Vac Start up delay typ 400ms see Fig 3 2 Rise time typ 60ms at 24V 20A const current load 0mF load capacitance see Fig 3 2 typ 240m...

Page 5: ...INPUT INRUSH CURRENT A NTC inrush limiter which is bypassed by a relay contact during normal operation limits the input inrush current after turn on of the input voltage Inrush current max 32Apeak 40...

Page 6: ...tage 13 5Vdc see Fig 6 1 Short circuit current min 21A load impedance 50mOhm see Fig 6 1 max 25A load impedance 50mOhm see Fig 6 1 typ 8 1A average R M S current load impedance 50mOhm see Fig 6 1 Outp...

Page 7: ...90 230Vac Input Voltage 50 60 Hold up Time 70 a b c d a 24V 10A typ b 24V 10A min c 24V 20A typ d 24V 20A min 5 Hold up Time Zero Transition Output Voltage Input Voltage 8 DC OK RELAY CONTACT This fea...

Page 8: ...and 25 C 230Vac MTBF SN 29500 IEC 61709 482 000h at 24V 20A and 40 C 230Vac 894 000h at 24V 20A and 25 C 230Vac MTBF MIL HDBK 217F 207 000h at 24V 20A and 40 C 230Vac Ground Benign GB40 279 000h at 24...

Page 9: ...ructed and suitable for field and factory wiring Input and output DC OK Signal Type Screw terminals Push in terminals Solid wire max 6mm2 max 1 5mm2 Stranded wire max 4mm2 max 1 5mm2 American Wire Gau...

Page 10: ...wer com Phone 49 89 9278 0 Germany 10 19 13 FRONT SIDE AND USER ELEMENTS Fig 13 1 Front side A Input Terminals screw terminals N L Line input PE Protective Earth input B Output Terminals screw termina...

Page 11: ...200Vac 140Vac 50 of 200Vac 100Vac 1000ms 500ms 200ms Criterion A Criterion C Criterion C Powerful transients VDE 0160 over entire load range 750V 0 3ms Criterion A Criterions A Power supply shows norm...

Page 12: ...to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 15 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 30W 1000m or 5 C 1000m 2000m 6500ft see Fig 15 2 Over...

Page 13: ...s down and automatically attempts to restart Class of protection I According to IEC 61140 A PE Protective Earth connection is required Ingress protection IP 20 According to EN IEC 60529 Over temperatu...

Page 14: ...ucting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000V...

Page 15: ...eclaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Duration 3 weeks which simulates a service life of at least 10...

Page 16: ...ICAL DIMENSIONS AND WEIGHT Width 49mm 1 93 Height 124mm 4 88 Depth 124mm 4 88 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 620g 1 37lb...

Page 17: ...dancy module which can be used to build 1 1 and N 1 redundant systems It is equipped with two input channels which can be connected to power supplies with up to 10A output current and one output which...

Page 18: ...breaker should be used 22 3 PARALLEL USE TO INCREASE OUTPUT POWER Do not use the power supply in parallel to increase the output power 22 4 PARALLEL USE FOR 1 1 REDUNDANCY Power supplies can be parall...

Page 19: ...ng capacitive and inductive loads If extreme large capacitors such as EDLCs electric double layer capacitors or UltraCaps with a capacitance larger than 1 5F are connected to the output the unit might...

Reviews: