ML120.244
MiniLine-2
24V,
5A,
S
INGLE
P
HASE
I
NPUT
4.
I
NPUT
I
NRUSH
C
URRENT
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
max.
37A
peak
40°C ambient, cold start
typ.
28A
peak
40°C ambient, cold start
typ.
23A
peak
25°C ambient, cold start
Inrush energy
typ.
1A
2
s
40°C ambient, cold start
Fig. 4-1
Input inrush current, typical behavior
230Vac input, 24V 5A output, 25°C ambient
Fig. 4-2
Input inrush current, zoom into first peak
230Vac input, 24V 5A output, 25°C ambient
Output
Voltage
20V/DIV
Input Voltage
- 500V/DIV
Input
Current
10A/DIV
40ms/DIV
Ipeak = 23A
Input Current
- 5A/DIV
1ms/DIV
5.
DC-I
NPUT
Do not operate this power supply with DC-input voltage. Use the ML120.241 unit instead.
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/21