ML120.244
MiniLine-2
24V,
5A,
S
INGLE
P
HASE
I
NPUT
3.
AC-I
NPUT
AC input
nom.
AC 200-240V
-15% / +10%
Allowed mains networks
TN/ TT/ IT-mains
AC input range
170-264Vac
continuously allowed
0-170Vac
no damage to the unit
264–300Vac
<
0.5s
Allowed voltage L or N to earth
max. 300Vac
continuously allowed, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Input current (rms)
typ.
1.07A
Power factor
*)
typ.
0.54
at 24V, 5A see Fig. 3-4
Crest factor
**)
typ.
4.0
at 24V, 5A
Start-up delay
typ.
80ms
Rise time
typ.
65ms
at 24V, 5A const. current load, 0mF load
capacitance, Fig. 3-2
175ms
at 24V, 5A const. current load, 5mF load
capacitance
Turn-on overshoot
max.
200mV
Turn-on voltage
typ.
158Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
134Vac
steady-state value, see Fig. 3-1
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage range
Fig. 3-2
Turn-on behavior, definitions
Turn-on
170V
Rated input range
V
IN
P
OUT
264Vac
Shut
-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3
Input current vs. output load at 24V
Fig. 3-4
Power factor vs. output load at 24V
5A
0.5 1 1.5 2 2.5 3 3.5 4 4.5
0
0.2
0.4
0.6
0.8
1.0
1.2
1.4A
Output Current
Input Current, typ.
Power Factor, typ.
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A
0.40
0.45
0.50
0.55
0.60
0.65
Output Current
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/21