Power supplies of the exact same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 
with a potential above 60Vdc are not SELV any more and can be dangerous. 
Such voltages must be installed with a protection against touching. 

Earthing of the output is required when the sum of the output voltage is 
above 60Vdc. 

Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals. 

Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard 
mounting orientation (input terminals on the bottom and output terminals on top of the unit).  

Be aware that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 

 

22.10.

 

O

PERATION ON 

T

WO 

P

HASES

 

2

40V 

+10%

 max.

Fuse

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

The power supply can also be used on two-phases of a three-phase-system. 
A phase-to-phase connection is allowed as long as the supplying voltage is 
below 240V

+10%

. Use a fuse or a circuit breaker to protect the N input. The 

N input is not internally protected and is in this case connected to a hot 
wire. Appropriate fuses or circuit breakers are specified in section 0 
“External Input Protection”. 

 

22.11.

 

U

SE IN A 

T

IGHTLY 

S

EALED 

E

NCLOSURE

 

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher 
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. 

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. 

The power supply is placed in the middle of the box; no other heat producing items are inside the box. 

Enclosure: 

 

 

Rittal Type IP66 Box PK 9510 100, plastic, 130x130x99mm 

Input: 

   230Vac 

 

 

Case A:

 

Load: 

 

   24V, 

5A; 

load 

is placed outside the box 

Temperature inside the box:  

62.4°C  (in the middle of the right side of the power supply with a distance of 1cm) 

Temperature outside the box:  

23.5°C 

Temperature rise: 

 

38.2K 

Case B:

 

Load:    

 

 

24V, 4A; (=80%) load is placed outside the box 

Temperature inside the box:  

54.8°C  (in the middle of the right side of the power supply with a distance of 1cm) 

Temperature outside the box:  

22.8°C 

Temperature rise: 

 

32.0K 

Apr. 2013 / Rev. 1.1  DS-ML120.244-EN  
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

20/21

Summary of Contents for MiniLine-2 Series

Page 1: ...vironment Besides the cost optimized ML120 244 two additional units are available in the ML120 series The ML120 CLASS2 fulfills the NEC Class 2 requirements and the ML120 241 is the standard product w...

Page 2: ...housing is patent by PULS US patent No US D442 923S No part of this document may be reproduced or utilized in any form without permission in writing from the publisher TERMINOLOGY AND ABREVIATIONS PE...

Page 3: ...le another power supply WARNING Risk of electrical shock fire personal injury or death Do not use the power supply without proper grounding Protective Earth Use the terminal on the input block for ear...

Page 4: ...down voltage typ 134Vac steady state value see Fig 3 1 The power factor is the ratio of the true or real power to the apparent power in an AC circuit The crest factor is the mathematical ratio of the...

Page 5: ...t Inrush energy typ 1A2 s 40 C ambient cold start Fig 4 1 Input inrush current typical behavior 230Vac input 24V 5A output 25 C ambient Fig 4 2 Input inrush current zoom into first peak 230Vac input 2...

Page 6: ...ll output voltage cannot be maintained and the output voltage will drip to lower values Detailed curves can be found in chapter22 1 Output power nom 120W Short circuit current min 7 8A load impedance...

Page 7: ...ing this time Fig 7 1 Hold up time vs input voltage Fig 7 2 Shut down behavior definitions 0 15 30 75 90ms 200 210 230 240 260Vac Hold up Time 45 60 a b c d 220 Input Voltage 250 a 24V 2 5A typ b 24V...

Page 8: ...0 of the nominal load for the rest of the time Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 0 5 84 85 86 87 88 89 90 83 91 5A 2 2 5 4 1 3 Outp...

Page 9: ...t Terminals Screw terminals Dual terminals for the negative and positive pole Both poles are equal Positive output Negative return output B Input Terminals Screw terminals L Phase Line input N Neutral...

Page 10: ...and 40 C 96 000h at 24V 2 5A and 40 C 106 000h at 24V 5A and 25 C MTBF SN 29500 IEC 61709 T B D at 24V 5A and 40 C T B D at 24V 5A and 25 C MTBF MIL HDBK 217F T B D at 24V 5A 40 C Ground Benign GB40 T...

Page 11: ...est During the test minor temporary impairments may occur which will be corrected by the power supply itself C Temporary loss of function is possible Power supply may shut down and restarts by itself...

Page 12: ...er voltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release a...

Page 13: ...Hz TN TT mains IT mains Double or reinforced insulation 17 DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground Type and factory tests are conducted by the manu...

Page 14: ...vel 3 in U S A UL 60950 1 and Canada C22 2 No 60950 1 E File E137006 Marine pending Marine and offshore applications environmental category C EMC2 GL Germanischer Lloyd classified GOST P pending Certi...

Page 15: ...he DIN rail height must be added to the unit depth 103mm to calculate the total required installation depth Installation Clearances See chapter 2 Fig 20 1 Front view Fig 20 2 Side view Apr 2013 Rev 1...

Page 16: ...hold up time DC Buffer Unit s Power Supply Load AC 21 2 REDUNDANCY MODULES The MLY10 241 is a dual redundancy module which has two diodes with a common cathode included It can be used for various pur...

Page 17: ...ow typical voltage dips Fig 22 1 Peak loading with 2x the nominal current for 50ms typ Fig 22 2 Peak loading with 5x the nominal current for 5ms typ 10ms DIV Output Voltage Output Current 24 5V 0A 10A...

Page 18: ...load current between the power supplies Usually the power supply with the higher adjusted output voltage draws current until it goes into current limitation This means no harm to the power supply as l...

Page 19: ...ng redundant power systems a Use separate input fuses for each power supply b Use separate mains systems for each power supply whenever it is possible c Monitor the individual power supply units A mon...

Page 20: ...ed as long as the supplying voltage is below 240V 10 Use a fuse or a circuit breaker to protect the N input The N input is not internally protected and is in this case connected to a hot wire Appropri...

Page 21: ...ended output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 5 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outp...

Reviews: