CS5.243
C-Line
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Nov. 2020 / Rev. 2.1 DS-CS5.243-EN
All parameters are specified at 24V, 5A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/26
7.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
Hold-up Time
typ.
109ms
165ms
at 24V, 2.5A, see Fig. 7-1
min.
87ms
135ms
at 24V, 2.5A, see Fig. 7-1
typ.
50ms
80ms
at 24V, 5A, see Fig. 7-1
min.
39ms
63ms
at 24V, 5A, see Fig. 7-1
typ.
37ms
62ms
at 24V, 6A, see Fig. 7-1
min.
30ms
49ms
at 24V, 6A, see Fig. 7-1
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
25
50
150ms
85
100
120 132Vac
Hold-up
Time
100
75
125
Input Voltage
a) 24V 2.5A typ.
b) 24V 2.5A min.
c) 24V 5A typ.
d) 24V 5A min.
e) 24V 6A min.
a
b
c
d
e
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.