CS5.243
C-Line
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Nov. 2020 / Rev. 2.1 DS-CS5.243-EN
All parameters are specified at 24V, 5A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/26
3.
AC-I
NPUT
AC input
nom.
AC 100-120V
±10%
Mains network systems
TN, TT or IT
AC input range
90-132Vac /
85-90Vac
132-150Vac
continuous operation
short-tem or with reduced output current, see Fig. 3-5.
max. 500ms
Allowed voltage L or N to earth
max.
300Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
60Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
55Vac
steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 22.3.
AC 100V
AC 120V
Input current
typ.
2.23A
1.88A
at 24V, 5A, see Fig. 3-3
Power factor
*)
typ.
0.6
0.59
at 24V, 5A, see Fig. 3-4
Crest factor
**)
typ.
2.9
3.1
at 24V, 5A
Start-up delay
typ.
120ms
120ms
Rise time
typ.
8ms
8ms
at 24V, 5A const. current load, 0mF
load capacitance, see Fig. 3-2
typ.
25ms
25ms
at 24V, 5A const. current load, 5mF
load capacitance,, see Fig. 3-2
Turn-on overshoot
max.
400mV
400mV
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage ranges
Fig. 3-2
Turn-on behavior, definitions
Tur
n-
on
(85) 90
V
IN
P
OUT
150Vac
Shut
-down
132
Rated Input
Range
Start-up
delay
Rise
Time
O
ve
rs
hoot
- 5%
Output
Voltage
Input
Voltage