![Puls DIMENSION CS5.243 Manual Download Page 18](http://html1.mh-extra.com/html/puls/dimension-cs5-243/dimension-cs5-243_manual_1624261018.webp)
CS5.243
C-Line
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Nov. 2020 / Rev. 2.1 DS-CS5.243-EN
All parameters are specified at 24V, 5A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
18/26
18.
A
PPROVALS AND
F
ULFILLED
S
TANDARD
UL 508
UL Certificate
Listed equipment for category NMTR - Industrial Control
Equipment
Applicable for US and Canada
E-File: E198865
IEC 60950-1
CB Scheme Certificate
General safety requirements for Information Technology
Equipment (ITE)
UL 60950-1
UL Certificate
Recognized component for category QQGQ - Information
Technology Equipment (ITE)
Applicable for US and Canada
E-File: E137006
Class I Div 2
CSA Certificate
Power Supplies for Hazardous Location
Applicable for Canada and US
CSA Class: 5318-01 (Canada), 5318-81 (USA)
Temperature Code: T3
Groups: A, B, C and D
Marine (DNV GL)
DNV-GL Certificate
DNV-GL Type approved product
Certificate: TAA00001ST
Temperature: Class B
Humidity: Class B
Vibration: Class C
EMC: Class A
Enclosure: Class A
Marine (ABS)
ABS Design Assessment Certificate
ABS (American Bureau of Shipment) assessed product
Certificate: 17-HG1599236-PDA
ISA-71.04-1985
Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb
Cl2: 20ppb
SO2: 300ppb
Test Duration: 3 weeks, which simulates a service life of at
least 10 years.
VDMA 24364
Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and test class C1 according to VDMA
24364-C1-L/W for solvents and water-based paints