CS5.243
C-Line
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Nov. 2020 / Rev. 2.1 DS-CS5.243-EN
All parameters are specified at 24V, 5A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/26
P
OWER
S
UPPLY
AC 100-120 Single-Phase Input
Width only 32mm
Efficiency up to 90.0%
Easy Fuse Breaking due to High Overload Peak Current
20% Output Power Reserves
Full Power up to +60°C
3 Year Warranty
G
ENERAL
D
ESCRIPTION
The DIMENSION C-Line units are cost optimized power
supplies without compromising quality, reliability and
performance. The C-Line is part of the DIMENSION
power supply family, existing alongside the high
featured Q-Line.
The CS5.243 includes all the essential basic functions and
the devices have a power reserve of 20%. This extra
current may even be used continuously at temperatures
up to +45°C.
The most important features are the small size, high
efficiency and the wide temperature range.
The unit also has an input for 100-120V mains only. This
supports regional applications and offers additional cost
savings without sacrificing functionality.
High immunity to transients and power surges as well as
low electromagnetic emission and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.
S
HORT
-
FORM
D
ATA
Output voltage
DC 24V
Adjustment range
24 - 28V
Output current
5A
at 24V, amb <60°C
6A
at 24V, amb <45°C
4.3A
at 28V, amb <60°C
5.1A
at 28V, amb <45°C
Output power
120W
ambient <60°C
144W
ambient <45°C
Output ripple
< 50mVpp
20Hz to 20MHz
AC Input voltage
AC 100-120V
±10%
Mains frequency
50-60Hz
±6%
AC Input current
1.88A
at 120Vac
DC Input voltage
-
not allowed
Power factor
0.59
at 120Vac
AC Inrush current
45A peak
at 120Vac
Efficiency
90.0%
at 120Vac
Losses
13.5W
at 120Vac
Temperature range -10°C to +70°C operational
Derating *)
3W/°C
+60 to +70°C
Hold-up time
78ms
at 120Vac
Dimensions
32x124x117mm WxHxD
Weight
500g / 1.1lb
O
RDER
N
UMBERS
Power Supply
CS5.243
24-28V Standard unit
(AC 100-120V-Version)
Accessory
ZM1.WALL
Wall mount bracket
ZM13.SIDE
Side mount bracket
YRM2.DIODE Redundancy module
M
ARKINGS
UL 508
UL 60950-1
Class I Div 2
IEC 60950-1
Marine