CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/27
3.
AC-I
NPUT
AC input
nom.
AC 100-120V /
200-240V ±10%
Auto-select input
Mains network systems
TN, TT or IT
AC input range
90-132Vac
180-264Vac
85- 90Vac
264-300Vac
lower input voltage range
upper input voltage range
short-term or with reduced output current, see Fig. 3-5
max. 500ms
no harm to the power supply with input voltages between 132 and 180Vac
Allowed voltage L or N to earth
max.
300Vac
continuous, according to IEC 62103
Input frequency
nom.
50
–
60Hz
±6%
Turn-on voltage
typ.
80Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
75Vac
steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 22.3.
AC 100V
AC 120V
AC 230V
Input current
typ.
4.34A
3.73A
2.23A
at 24V, 10A, see Fig. 3-3
Power factor
*)
typ.
0.61
0.59
0.51
at 24V, 10A, see Fig. 3-4
Crest factor
**)
typ.
2.6
2.8
3.3
at 24V, 10A
Start-up delay
typ.
700ms
800ms
850ms
Rise time
typ.
35ms
35ms
35ms
at 24V, 10A const. current load, 0mF
load capacitance, see Fig. 3-2
typ.
75ms
75ms
75ms
at 24V, 10A const. current load, 10mF
load capacitance,, see Fig. 3-2
Turn-on overshoot
max.
100mV
100mV
100mV
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1
Input voltage ranges
Fig. 3-2
Turn-on behavior, definitions
T
u
rn
-o
n
(85) 90
Rated input ranges
V
IN
P
OUT
264
180
S
h
u
t-d
o
w
n
132
Upper
range
Lower
range
300Vac
max.
500ms
Start-up
delay
Rise
Time
O
v
e
rs
h
o
o
t
- 5%
Output
Voltage
Input
Voltage