Pullin Evolution Solar PES190 Installation And Servicing Instructions Download Page 5

5

5

Worked example of discharge pipe sizing

The example below is for a G1/2 temperature relief

valve with a discharge pipe (D2) having 4 No. elbows

and length of 7m from the tundish to the point of

discharge.

From Table 4:

Maximum resistance allowed for a straight length of

22mm copper discharge pipe (D2) from a G1/2

temperature relief valve is 9.0m.

DISCHARGE PIPEWORK

It is a requirement of Building Regulation G3 that any

discharge from an unvented system is conveyed to

where it is visible, but will not cause danger to

persons in or about the building. The tundish and

discharge pipes should be fitted in accordance with

the requirements and guidance notes of Building

Regulation G3. The G3 Requirements and Guidance

section 3.9 are reproduced in the following sections.

Information Sheet No. 33 available from the British

Board of Agrément gives further advice on discharge

pipe installation. For discharge pipe arrangements

not covered by G3 Guidance or BBA Info Sheet No.33

advice should be sought from your local Building

Control Officer.

G3 REQUIREMENT

“...there shall be precautions...to ensure
that the hot water discharged from safety
devices is safely conveyed to where it is
visible but will not cause danger to
persons in or about the building.”

G3 GUIDANCE SECTION 3.9

The discharge pipe (D1) from the vessel up
to and including the tundish is generally
supplied by the manufacturer of the hot
water storage system. Where otherwise,
the installation should include the
discharge pipe(s) (D1) from the safety
device(s). In either case the tundish
should be vertical, located in the same
space as the unvented hot water storage
system and be fitted as close as possible
and within 500mm of the safety device e.g.
the temperature relief valve.
The discharge pipe (D2) from the tundish
should terminate in a safe place where
there is no risk to persons in the vicinity of
the discharge, preferably be of metal and:
a.  be at least one pipe size larger than the
nominal outlet size of the safety device
unless its total equivalent hydraulic
resistance exceeds that of a straight pipe
9m long i.e. discharge pipes between 9m
and 18m equivalent resistance length
should be at least two sizes larger than
the nominal  outlet size of the safety
device, between 18 and 27m at least 3
sizes larger , and so on. Bends must be
taken into account in calculating the flow
resistance. Refer to Diagram 1, Table 1 and
the worked example.
An alternative approach for sizing dis-
charge pipes would be to follow BS
6700:1987 Specification for design instal-
lation, testing and maintenance of ser-
vices supplying water for domestic use
within buildings and their curtilages,
Appendix E, section E2 and table 21.
b.  have a vertical section of pipe at least
300mm long, below 

t

he tundish before

any elbows or bends in the pipework.
c.  be installed with a continuous fall.
d.  have discharges visible at both the
tundish and the final point of discharge
but where this is not possible or is practi-
cally difficult there should be clear
visibility at one or other of these locations.
Examples of acceptable discharge ar-
rangements are:

i.   ideally below a fixed grating and
above the water seal in a trapped gully.
ii.  downward discharges at low level;
i.e. up to 100mm above external surfaces
such as car parks, hard standings,
grassed areas etc. are acceptable pro-
viding that where children may play or
otherwise come into contact with dis-
charges a wire cage or similar guard is
positioned to prevent contact, whilst
maintaining visibility.
iii. discharges at high level; e.g. into a
metal hopper and metal down pipe with
the end of the discharge pipe clearly
visible (tundish visible or not) or onto a
roof capable of withstanding high tem-
perature discharges of water and 3m
from any plastics guttering system that
would collect such discharges (tundish
visible).
iv. where a single pipe serves a number
of discharges, such as in blocks of flats,
the number served should be limited to
not more than 6 systems so that any
instalation discharging can be traced
reasonably easily. The single common
discharge pipe should be at least one
pipe size larger than the largest indi-
vidual discharge pipe (D2) to be con-
nected. If unvented hot water storage
systems are installed where discharges
from safety devices may not be appar-
ent i.e. in dwellings occupied by blind,
infirm or disabled people, consideration
should be given to the installation of an
electronically operated device to warn
when discharge takes place.

Note: 

The discharge will consist of

scalding water and steam. Asphalt, roof-
ing felt and non-metallic rainwater
goods may be damaged by such dis-
charges.

Summary of Contents for PES190

Page 1: ...ion Solar is a purpose designed unvented solar water heater The unit has a stainless steel inner vessel which ensures an excellent standard of corrosion resistance The outer casing is a combination of...

Page 2: ...ion should be placed between the 2 pieces of the cold water combination valve assem bly see Fig 1 Outlets situated higher than the Pullin Evolution Solar will give outlet pressures lower than that at...

Page 3: ...sion vessel wall mounting bracket is supplied for this purpose NOTE DONOTUSETHEPOTABLEWATEREXPAN SIONVESSELSUPPLIEDWITHTHEPULLIN EVOLUTIONSOLARFORANYOTHERPURPOSE IT ISNOTSUITABLEFORUSEONASOLAR PRIMARY...

Page 4: ...F E NOMINAL CAPACITY litres TYPE DIMENSIONS mm A B C D 2 Direct heating times assume use of lower element only and auxillary cylinder volume being heated SURFACE AREA m RATING kW RECOVERY mins 1 Recov...

Page 5: ...utlet size of the safety device between 18 and 27m at least 3 sizes larger and so on Bends must be taken into account in calculating the flow resistance Refer to Diagram 1 Table 1 and the worked examp...

Page 6: ...ny other purpose The tundish should not be located adjacent to any electrical components Valve outlet size Minimum size of discharge pipe D1 Minimum size of discharge pipe D2 from tundish Maximum resi...

Page 7: ...INDIRECT SYSTEM CONTROLS JUNCTION BOX GREEN YELLOW BROWN BLUE 3 DIRECT THERMOSTAT B A 1 1 2 2 3 INDIRECT THERMOSTAT INDIRECT THERMAL CUT OUT EXPANSION VESSEL COLD WATER COMBINATION VALVE 2 PIECE T P R...

Page 8: ...ls which must be installed as per the manufacturers instruc tions CONTROLOFSOLARPRIMARYCIRCUIT Temperature control of the Pullin Evolution Solar must be carried out using a suitable proprietory Solar...

Page 9: ...ry heating source boiler connections are made to the terminal block located under the terminal cover mounted on the side of the unit The supply cable s must be routed through the cable grip s in the t...

Page 10: ...SUPPLY ALL EARTH CONNECTIONS MUST BE CONNECTED BACK TO THE MAINS EARTH SUPPLY CONTROL CIRCUIT FOR AUXILLARY HEATING BOILER ONLY SEPARATE CONTROLS WILL BE REQUIRED FOR THE SOLAR PRIMARY CIRCUIT PROGRA...

Page 11: ...ing the lever on the motor housing to the FLUSHING ONLY setting When the circuit is full return the lever to the NORMAL USE position Switch on the boiler ensure the programmer is set to Domestic Hot W...

Page 12: ...stat and thermal cut out DIRECTMODELS Open the cover s to the immersion heater housing s and disconnect wiring from the thermostat mounted on top of the immersion heater s Remove the thermostat by car...

Page 13: ...FTHESAFETY VALVESFITTEDTOTHEPULLINEVOLUTION SOLARSYSTEM IFAFAULTISSUSPECTED CONTACTACOMPETENTINSTALLER TEMPERATURECONTROLS SOLAR Temperature control of the solar primary coil is by means of solar diff...

Page 14: ...6 Terminal cover 95 614 089 Indirect controls Indirect thermostat 95 612 697 Indirect Thermal cut out and Solar Cut out 95 612 698 Motorised valve 2 port 95 605 049 Terminal housing 95 614 090 4 Way t...

Page 15: ...required 1 DIRECT immersion heater not switched on 1 Check and switch on 2 DIRECT immersion heater thermal cut out has operated 2 Check Reset by pushing button 3 INDIRECT programmer set to Central Hea...

Page 16: ...register the product It has been installed in the United Kingdom The expansion vessel is guaranteed for a period of 2 years from the date of purchase The Pullin Evolution Solar s com ponents immersion...

Page 17: ...uture reference 2 This Log Book is to be completed in full by the competent person s who commissioned the equipment and then handed to the customer When this is done the Log Book is a commissioning ce...

Page 18: ...ER DATE REGISTEREDOPERATIVEIDCARDNO IFAPPLICABLE COMMISSIONING ENGINEER IF DIFFERENT COMPANYNAME ADDRESS ENGINEERNAME TELEPHONENUMBER DATE REGISTEREDOPERATIVEIDCARDNO IFAPPLICABLE APPLIANCE TIME CONTR...

Page 19: ...YES NO IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE YES NO WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED BAR WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED HAS THE EXPAN...

Page 20: ...EL NO COMMENTS SIGNATURE SERVICE 2 DATE ENGINEER NAME COMPANY NAME TEL NO COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL NO COMMENTS SIGNATURE SERVICE 5 DATE ENGINEER NAME COMPANY NA...

Reviews: