background image

7

Ex-zone

If the cable ends are connected 

inside

 the Ex-

zone, the ignition protection type must not be 
impaired with due consideration being given to 
the intended use.

Prerequisites for safe operation of the signal anal-
ysis units and the sensors:

Responsibility 

Each intrinsically safe company has an authorized 
EX protection representative who is solely aware 
which conditions, norms, etc. must be observed 
in his company. Only the specialist personnel he 
authorizes are allowed to work on the system.

The following installation recommendations must 
be authorized by the EX protection representative: 

Limiting device VIB 3.550

 

– The limiting device is to be installed in a switch

cabinet or housing (at least IP 20).

 

– The intrinsic connections for the limiting device

must be installed at a distance of at least 50 mm 
from non-intrinsically safe circuits.

 

– Potential equalization (PA) is to be applied first

and must not be looped through.

 

– The signal analysis unit must be grounded with

potential equalization at the location of the lim-
iting device.

 

– The limiting device is the only grounded point of 

the intrinsically safe circuit in the Ex-zone.

 

– Potential equalization is to be established be-

tween the limiting device and monitored ma-
chines.

Sensor

 

– Sensors of the series VIB 6.1xy DEX are electri-

cally insulated. Sensors and protective terminal
housings must be reliably protected against
physical contact. To do this, they must be fit-
ted with the IP68 option or with protective caps
beyond the insulated position and fixed with
clamp rings

Wiring to potential equalization

 

– A line resistance of <120 mOhm is recommend-

ed for interference protection reasons (=1.5
mm²/10 m).

 

– Due consideration is to be given to personnel,

goods, lightning, explosion protection - as well
as other protection types where appropriate -
for the respective customer, trade association,
insurer, state, federal government etc.

 

– In this regard, the relevant implementation pro-

visions are to be observed. This also applies to
provisions relating to the safety of the connec-
tion type. In accordance with these provisions,
wiring is only to be carried out by an approved
specialist who is insured for such purposes.

Connector cable 

The following applies to 

coaxial

 cable: 

 

– The shield is laid on the shield terminal of the

limiting device. PA and the shield terminal are
connected with each other.

 

– With regard to extension by means of a metallic

protective terminal housing, the shield must not
have any electrical contact with the housing.
The shield is to be electrically insulated.

 

– The metallic protective terminal housing is to be

protected against being touched by means of
heat-shrink tubing or grounding with PA.

The following applies to 

triaxial

 extension cable:

 

– The outer shield is laid on PA of the limiting de-

vice.

 

– With regard to extension by means of a metallic

protective terminal housing, the outer shield is
not laid on the protective terminal housing but
is reliably insulated. Alternatively, the metallic
housing can be insulated by means of heat-
shrink tubing.

 

– With regard to outward-facing cable interfaces,

the outer shield is insulated by means of heat-
shrink tubing or with an insulating cap.

Insulate shield!

Device side:

Connect outer 

shield with PA!

VIB 3.550

coaxial 

PA = Potential equalization

coaxial 

coaxial 

triaxial

triaxial

triaxial

Summary of Contents for FLUKE VIB 6.12 Series

Page 1: ...Accelerometer Industrial VIB 6 12x VIB 6 14x Installation and Operation ...

Page 2: ...he Ex zone Only sensors of series VIB 6 1 DEX are permit ted to be operated in the Ex zone Sensors of series VIB 6 1 DEX are only to be connected to certified intrinsically safe circuits giving due consideration to the following max imum values Ui 24 V Pi 300 mW Ci 15 nF Li negli gibly small The permissible ambient temperature range is between 30 C and 80 C 22 F 176 F The European installation reg...

Page 3: ...P 67 w straight protective cap and clamp rings IP 68 w cable option VIB 6 760 VIB 6 761 only for series VIB 6 1 IP Shock resistance 250 kms 2 25000 g 50 kms 2 5000 g Temperature sensitivity 0 05ms 2 K 0 01ms 2 K Magnetic sensitivity 5ms 2 T at 50 Hz 1ms 2 T at 50 Hz Base strain sensitivity 0 1ms 2 µm m Temperature range w cable VIB 90093 1 w cable VIB 90007 30 C 80 C 22 F 176 F VIB 6 1 DEX 40 C F ...

Page 4: ...ing out the hole Solvent for degreasing Threadlocker LOCTITE 243 Select the point of installation The drilled hole must have direct connection to the bearing carrier if the sensor should measure shock pulse signals Minimum distance between the drilled hole and protruding edges of the housing must be 35 mm A Allow adequate clearance to attach the wrench Note Ensure that a hole can be drilled at the...

Page 5: ...he adhesive for use Apply the adhesive with a wooden spatula evenly to the base of the mounting adapter and the bonding location approx 1 mm thick I Affix mounting adapter Press the adapter gently against the bonding lo cation and turn it to evenly distribute the adhe sive If applicable screw in the centering pin J Do not remove excess adhesive If necessary apply additional adhesive around the bon...

Page 6: ...a cable duct or protective tube Use cable ties and Velcro fasteners to fix the ca bles in place Do not lay cables parallel to power lines Adhere to the minimum spacing 1 m Lay a loop with sufficient reserve traction ahead of a cable gland Label the cable ends to avoid getting them mixed up Extend the cable Observe the maximum cable lengths see the device installation manual Use appropriate coaxial...

Page 7: ...ntial equalization A line resistance of 120 mOhm is recommend ed for interference protection reasons 1 5 mm 10 m Due consideration is to be given to personnel goods lightning explosion protection as well as other protection types where appropriate for the respective customer trade association insurer state federal government etc In this regard the relevant implementation pro visions are to be obse...

Page 8: ... C Protective terminal housing plastic D Protective terminal housing metallic mounted and insulated housing at PA E Outer shield not laid F Protective cap w clamp ring or IP68 cable option VIB 6 760 6 761 PA potential equalization Connection examples for the Ex zone VIBSCANNER EX PA PA CMS without EX protection Um 250V PE Not connected PA VIB 3 550 50 mm EX i Coaxial VIBXPERT EX Machine A C D Tria...

Reviews: