10 SOLAREG II technical data
Casing
Material
100% recyclable ABS casing for wall mounting
Dimensions (L x W x H) in mm,
weight
175 x 134 x 56; approx. 360 g
Protection class
IP20 according to DIN 40050
Electrical specifications
Supply voltage
AC 230 V/50 Hz, -10 – +15%
Radio interference class
N (as defined by VDE 0875)
Max. cable cross-section, 230 V
connections
2.5 mm² fine-/single-wire
Temperature sensor
measuring range
PT1000, 1 kΩ at 0 °C
- 30 °C .. +250 °C
Test voltage
4 kV 1 min according to EN 60730/DIN, VDE
0631, IEC 60664/IEC
Output voltage
Power per output
Control signal PWM (O1):
Control signal ANA (O1:
230 V AC
1 A / approx. 230 VA for cos φ = 0.7-1.0
2 kHz, max. 10 mA
0..10 V, max. 5 mA
Fuses
Fine-wire fuses 5 x 20 mm, 2A (T)
2 amperes, time lag fuse
Other
Operating temperature
0 – + 50 °C
Storage temperature
-10 – + 65 °C
Humidity
max. 60 %
11 PT1000 resistance table
Temperature sensors can be checked for proper function by using an ohmmeter
and consulting the following temperature resistance table:
Temperature
in °C
Resistance in
ohms
Temperature
in °C
Resistance in
ohms
-30
882
60
1232
-20
921
70
1271
-10
960
80
1309
0
1000
90
1347
10
1039
100
1385
20
1077
120
1461
30
1116
140
1535
40
1155
200
1758
50
1194
Specifications subject to