IPS2 24 VDC Configuration Settings
Table 1:
Explanation of the Protrol IPS2 24 VDC Configuration settings.
Parameter
Range
Unit
Default
Comment
General Settings
Reignition time [ms]
0..10000
ms
2000
A reoccurring fault within the reignition time window
overrides the EF time rotary switch and sets the operate
time to a minimum. 0 disables the reigniting faults function
LED flashing time [min]
0..1440
min
120
The flashing time of the external LED in minutes also is used
to acknowledge the front panel indication LEDs.
Analogue update [s]
0..65535
s
0
Cyclic update of analogue values. No cyclic update if the set
value is 0, however, the deadband is activated instead
CT ratio
50..1200
-
300
Relay choice
0..3
-
0
0
:
X2: Start, X3: Trip
.
1
:
X2: EF Trip, X3: OC Trip
2
:
X2: Watchdog, X3: Trip (Hardware version 3 only)
3
:
X2 and X3: General Trip
Operation mode
0..1
Bit 5: On
All other: Off
Checkbox 7
:
DIR bit in balanced mode
Checkbox 6
:
Balanced mode
Checkbox 5
:
Send analog objects
Checkbox 4
:
Time tag
Checkbox 3
:
Not used
Checkbox 2
:
Not used
Checkbox 1
:
See relay choice
Checkbox 0
:
See relay choice
OC level shift factor
0..8
-
0
0
:
Not used
1
:
Trip level divided by 2
2
:
Trip level divided by 4, etc.
IEC 60870-5-101 Communication
Configuration
RTU Link Address
1..255
-
1
Common Address
1..65534
-
1
Common Address of ASDU
RTU Link Address size
1..2
-
1
Number of octets for RTU Link Address
Cause of Transmission size
1..2
-
2
Number of octets for Cause of Transmission
Common Address size
1..2
-
2
Number of octets for Common Address
Information Object Address size
1..3
-
3
Number of octets for Information Object Address
Baudrate
9600, 19200
bit/s
9600
Standard rates for the IEC-101 port