The I> pickup level setting is a per unit value related to the current transformer ratio.
Example:
300/1 ratio and pickup level 2.5 corresponds to a primary current level of
300 × 2.5 A = 750 A
The I
0
> pickup settings in Amperes are based on a current transformer ratio of 300/1. In the case a different
ratio is used the levels are scaled proportionally.
Example:
150/1 ratio and pickup level of 2 corresponds to a primary current setting of
150/300 × 2 A = 1 A
I>I>
Position
Pickup level [pu]
0
OFF
1
0.5
2
0.75
3
1.0
4
1.5
5
2.0
6
2.5
7
3
8-9
Not used
I>t
Position
Pickup delay [s]
0
0.04
1
0.1
2
0.2
3
0.4
4
0.6
5
0.8
6
1.0
7
2.0
8-9
Not used
I>I
0
>
Position
Pickup level [A]
0
OFF
1
1.0
2
1.5
3
2.0
4
2.5
5
3
6
5
7
10
8-9
Not used
I>t
Position
Pickup delay [s]
0
0.04
1
0.1
2
0.2
3
0.5
4
1.0
5
2.0
6
5.0
7
30
8-9
Not used