Remote controls
Part 4: Installation and Start-up
50
Installation location:
•
In reference / main living room of the heating circuit
(on an inside wall of the room).
•
Not in the vicinity of radiators or other heat dissipating
units.
•
Any, if the room sensor influence is switched off.
Installation:
•
Remove cap from underside of pedestal.
•
Secure the base at the installation location.
•
Connect the electrical connection cables.
•
Press the cap back on.
Sensor resistances FBR
DCF receiver
Electrical connection: Connector VII; 1,2
The controller is equipped with a connection option for a
DCF receiver.
When the DCF receiver is connected, the controller's clock
is updated daily at 3:20 a.m. and also 5 minutes after
switching on the power supply.
If the time is not automatically corrected from the specified
time, select a different installation site for the DCF (e.g.
another wall) and restart the controller (switch off the
power supply briefly).
PC
All system-specific parameters can be set and interrogated
using the
C
omfort
S
oft
parameterisation software. The
parameters can be saved, displayed graphically and
evaluated on the PC at predefined intervals. T connect to a
PC you need the optical adapter or CoCo PC active, which
also supports the sending of error messages by SMS and
the remote interrogation of controller data.
Temperature
FBR1
terminals 1-2
Switch in
position
q
FBR2
terminals 1-2
Room sensor
+10 °C
680
Ω
9.950
Ω
+15 °C
700
Ω
7.855
Ω
+20 °C
720
Ω
6.245
Ω
+25 °C
740
Ω
5.000
Ω
+30 °C
760
Ω
4.028
Ω