User Area
Part 2: Overview of display values and settings
22
*)
or, depending on function selected, heating circuit
T-POOL, T-DHW, T-FLOW DAY or T-FLOW NIGHT (see
page 38)
MODE
- - - - => The controller programming switch applies in this
case.
When setting an alternative operating mode this only
applies to the assigned heating circuit.
When the "
i
= Standby/OFF", and "
F
= Summer mode"
controller programming switch operating modes are set,
this has a reducing effect on all heating circuits and
consumer circuits in the entire system.
T-ROOM DES 1-3
Required room temperature setting
T-ROOM DES 1 => used in first enable time,
T-ROOM DES 2 => used in second enable time,
T-ROOM DES 3 => used in third enable time of active
heating program for this heating circuit.
T-REDUCED
Required room temperature setting during night reduction
T-ABSENCE
Required room temperature setting during holidays
Heating circuit I / II
Designation Value
range
Default
IV
MODE ----
,
i
,
F
1,
F
2,
B
,
B
- - - -
T-ROOM DES 1*
)
5°C - 40°C
20°C
T-ROOM DES 2
5°C - 40°C
20°C
T-ROOM DES 3
5°C - 40°C
20°C
T-REDUCED
*)
5°C - 40°C
10°C
T-ABSENCE
5°C - 40°C
15°C
T-LIMIT DAY
----, (-5)°C–40°C 19°C
T-LIMIT N
----, (-5)°C–40°C 10°C
HEATSLOPE
0.00 – 3.00
1,20
ADAPTION
00, 01 (OFF/ON) 00 = OFF
ROOMS-INFL
00 – 20
10
ADAP ROOM-T
(-5.0)K – (5.0)K
0,0 K
OPTIM HEAT
00, 01, 02
00
MAX OPT-TIME
0:00 – 3:00 [h]
2:00 [h]
ECONO OPTI
0:00 – 2:00 [h]
0:00 [h]
PC-ENABLE
0000 - 9999
0000
RETURN
Exit level using
Ä