N 93-602-00 Issue 1 

Page 7 of 10 

                © Protec Fire Detection PLC 2015 

4.3  Pre-alarm 

 

The Pre-alarm condition takes priority over faults. When a pre-alarm condition is activated the display 
shows all pipes commissioned (1, 2, 3 or 4). The Pre-

alarm text is represented as ‘Warning’. The figure 3.2 

below shows 4 pipes; where Pipe 1 and Pipe 2 are in Pre-

Alarm condition: ‘Warning’, Pipe 3 and Pipe 4 are 

in ‘Normal’ condition. The Pre-Alarm LED is illuminated, any commissioned outputs will activate and the fire 
condition is reported to the Protec Fire panel. 

 
 

 

Figure 4.3 ProPointPlus displaying Pre-Alarm condition 

 
 

The appointed ‘Responsible Person’ should investigate the relevant area following the official 
procedures for the building. Extreme care must be exercised at all times. 

 
 

Muting the buzzer 

 
The buzzer can be muted by pressing any button. 
 

 

Summary of Contents for ProPoint PLUS

Page 1: ...Protec Fire Detection plc Protec House Churchill Way Nelson Lancashire BB9 6RT ENGLAND 44 0 1282 717171 www protec co uk sales protec co uk PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL ...

Page 2: ...N 93 602 00 Issue 1 Page 2 of 10 Protec Fire Detection PLC 2015 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15 11 2015 ...

Page 3: ...This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling in accordance with the European Waste Electrical and Electronic Equipment Directive To dispose of old electrical or electronic ...

Page 4: ...plications ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator Each of the four plug in Scatter Camber Detectors SCD s detector use independent and integrated alarm decision making Complex algorithms are used to extend the range of particle detection confirm genuine alarms and...

Page 5: ...is in Fault Pre alarm or Fire providing the buzzer is enabled at commissioning The buzzer can be muted by pressing any button LED indicators are programmed to illuminate corresponding to a specific event The button functions are to navigate thought the commissioning menu and are therefore not a requirement for the user 4 1 Display Figure 4 1 ProPointPlus display detector normal Power LED Green Fir...

Page 6: ... in the centre of the display When more than one faults is reported the faults are automatically scrolled though each fault on the display The fault LED will be illuminated If the fault is pipe specific the pipe number is displayed in brackets next to the fault for example below shows 1 Airflow Fault describes an airflow fault on pipe 1 Figure 4 2 ProPointPlus displaying a fault condition Refer to...

Page 7: ...ipe 1 and Pipe 2 are in Pre Alarm condition Warning Pipe 3 and Pipe 4 are in Normal condition The Pre Alarm LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 3 ProPointPlus displaying Pre Alarm condition The appointed Responsible Person should investigate the relevant area following the official procedures for the buildin...

Page 8: ...presented as Fire The example picture below shows 4 pipes where Pipe 2 are in Fire condition Pipe 1 Pipe 3 and Pipe 4 are in Normal condition The Fire LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 4 ProPointPlus displaying Fire Alarm condition The building fire plan must be executed immediately Muting the buzzer The b...

Page 9: ...r a Protec distributor Link Fault The data RS485 path has failed Contact a Protec operative or a Protec distributor Output Override The inputs check to test option is active activated using the ProView exe PC software Contact a Protec operative or a Protec distributor Corrupt Settings Internal settings are outside the expected values Unit will default to factory settings Contact a Protec operative...

Page 10: ... LED Alarm Fire Red LED OLED Display Unit status Faults Pre Alarm and Fire and Commissioning menu Sensitivity A High B Enhanced C Normal Number sampling hole alternative to point type smoke detector Holes per pipe max Pre Alarm Level1 Fire Level1 A1 A2 A3 3 150 2 2 m 200 2 9 m B1 B2 B3 B4 B5 5 150 2 2 m 250 3 6 m C1 C2 C3 C4 C5 C6 C7 C8 8 150 2 2 m 250 3 6 m Prison 1 Max area coverage per pipe 800...