N 93-602-00 Issue 1 

Page 4 of 10 

                © Protec Fire Detection PLC 2015 

1.0  Scope of document 

This  document  details  the  user  information  for  the  Protec  ProPointPlus  Aspirating  Smoke  Detector  with 
specific attention to the basic system operations of the product. The Protec ProPointPlus Aspirating Smoke 
Detector  has  been  designed  and  manufactured  in  the  United  Kingdom  and  complies  fully  with  current 
standard dictating aspirating smoke detector design practice (EN54 parts 20). 
 

2.0  User Responsibilities 

The registered owner of the fire alarm system has specific responsibilities regarding the installation, testing 
and maintenance of the fire alarm system. 
 
BS5839  Pt  1:  2013  Section  7  states  that  the  user  of  the  fire  alarm  system  must  appoint  a  single  named 
person to supervise all matters regarding the fire alarm system. 
 
Summarised below are the responsibilities expected of the named person, 

 

It is strongly advised that a full copy of BS5839 Pt 1: 2013 is obtained and 
thoroughly read and understood. 

 
 

3.0  Introduction 

Aspirating detection is now a recognised solution for many different fire detection applications. ProPointPlus 
provides  up  to  four  separate  detectors  within  a  common  aspirator  enclosure  and  therefore  provides  four 
individually identifiable areas of detection per aspirator. 
 
Each  of the four plug in Scatter  Camber De

tectors (SCD’s) detector use independent and integrated alarm 

decision  making.  Complex  algorithms  are  used  to  extend  the  range  of  particle  detection,  confirm  genuine 
alarms and reduce unwanted alarms. 
 
Installation,  configuration  and  commissioning  of  the  ProPointPlus  detectors  is  very  simple  and  installer 
friendly. Configuration to either Class A, Class B or Class C sensitivity options is  achieved through a multi- 
function OLED display without the need for a PC connection. 
 
The features of the ProPointPlus are:  
 

 

High performance optical detection with 
optional enhanced CO detection. 
 

 

1 to 4 individual detectors. 

 

 

Protec 6000 series digital addressable 
protocol. 

 

 

Simple sensitivity configuration setup:     
Class A, Class B, Class C and Prison. 

 

 

On-board loop isolator. 

 

 

Common Fault output contact. 
 

 

5 Programmable output contacts.  

 

3 Programmable input contacts. 

 

 

Airflow monitoring per pipe. 

 

 

Variable blower speed control. 

 

 

Integral OLED display for fault reporting and 
ease of setup. 
 

 

Commissioning menu access code protected. 

 

 

Support multiple language menu functions. 

 

 

TCP/IP Network configurable.  

    

Summary of Contents for ProPoint PLUS

Page 1: ...Protec Fire Detection plc Protec House Churchill Way Nelson Lancashire BB9 6RT ENGLAND 44 0 1282 717171 www protec co uk sales protec co uk PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL ...

Page 2: ...N 93 602 00 Issue 1 Page 2 of 10 Protec Fire Detection PLC 2015 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15 11 2015 ...

Page 3: ...This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling in accordance with the European Waste Electrical and Electronic Equipment Directive To dispose of old electrical or electronic ...

Page 4: ...plications ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator Each of the four plug in Scatter Camber Detectors SCD s detector use independent and integrated alarm decision making Complex algorithms are used to extend the range of particle detection confirm genuine alarms and...

Page 5: ...is in Fault Pre alarm or Fire providing the buzzer is enabled at commissioning The buzzer can be muted by pressing any button LED indicators are programmed to illuminate corresponding to a specific event The button functions are to navigate thought the commissioning menu and are therefore not a requirement for the user 4 1 Display Figure 4 1 ProPointPlus display detector normal Power LED Green Fir...

Page 6: ... in the centre of the display When more than one faults is reported the faults are automatically scrolled though each fault on the display The fault LED will be illuminated If the fault is pipe specific the pipe number is displayed in brackets next to the fault for example below shows 1 Airflow Fault describes an airflow fault on pipe 1 Figure 4 2 ProPointPlus displaying a fault condition Refer to...

Page 7: ...ipe 1 and Pipe 2 are in Pre Alarm condition Warning Pipe 3 and Pipe 4 are in Normal condition The Pre Alarm LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 3 ProPointPlus displaying Pre Alarm condition The appointed Responsible Person should investigate the relevant area following the official procedures for the buildin...

Page 8: ...presented as Fire The example picture below shows 4 pipes where Pipe 2 are in Fire condition Pipe 1 Pipe 3 and Pipe 4 are in Normal condition The Fire LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 4 ProPointPlus displaying Fire Alarm condition The building fire plan must be executed immediately Muting the buzzer The b...

Page 9: ...r a Protec distributor Link Fault The data RS485 path has failed Contact a Protec operative or a Protec distributor Output Override The inputs check to test option is active activated using the ProView exe PC software Contact a Protec operative or a Protec distributor Corrupt Settings Internal settings are outside the expected values Unit will default to factory settings Contact a Protec operative...

Page 10: ... LED Alarm Fire Red LED OLED Display Unit status Faults Pre Alarm and Fire and Commissioning menu Sensitivity A High B Enhanced C Normal Number sampling hole alternative to point type smoke detector Holes per pipe max Pre Alarm Level1 Fire Level1 A1 A2 A3 3 150 2 2 m 200 2 9 m B1 B2 B3 B4 B5 5 150 2 2 m 250 3 6 m C1 C2 C3 C4 C5 C6 C7 C8 8 150 2 2 m 250 3 6 m Prison 1 Max area coverage per pipe 800...

Reviews: