93-520-20 Issue 3.3
Page 9 of 60
CirrusPro Engineer’s Manual
Maximum Coverage
Per Sample Head or Point:
30’ x 30’ (9.144m x 9.144m)
Number of Zones:
Pro 100
1 Zone
Pro 200
1 Zone
Pro 200+
1 Zone
Pro 200D
1 Zone
Pro 200D+
1 Zone
Pro 200DSC
Field Programmable up to 4 Zones
Pro
Field Programmable up to 4 Zones
Maximum Number of
Sampling Heads or Points:
100
Minimum Number of
Sampling Heads or Points:
2 per pipe
Alarm Thresholds:
4 per Zone
Sampling System DT
(Transport Time)
Maximum Allowed
Pro 100
120 Seconds
Pro 200
120 Seconds
Pro 200+
120 Seconds
Pro 200D
120 Seconds
Pro 200D+
120 Seconds
Pro 200DSC
1 Zone system 120 Seconds
2 Zone system 90 Seconds
3 Zone system 75 Seconds
4 Zone system 60 Seconds
Pro
1 Zone system 120 Seconds
2 Zone system 90 Seconds
3 Zone system 75 Seconds
4 Zone system 60 Seconds
Sampling System DT
(Transport Time)
Minimum Allowed:
6 Seconds (on Multi Zone systems)
Controls:
Push Buttons
Indicators
:
Pre-Alarm, Fire 1, Fire 2, Fire 3 LED’s
Power and Fault LED’s
LCD display for Particle levels, Alarm and Fault Text
Power Requirements
:
21-27V dc. Unit must be used with a UL 1481 Listed Power
supply
Contact Ratings
:
1A at 30V dc
4 Alarm relays per zone (Non-monitored volt free contacts)
1 Fault relay (Non-monitored volt free contact)
Outputs
:
Audible alert, RS232 Serial Computer Interface