93-520-20 Issue 3.3
Page 20 of 60
CirrusPro Engineer’s Manual
3.2.6 The Commissioning Menu
Clicking on ‘Commission’ on the toolbar displays the following list of items:
To complete the commissioning it is necessary to follow this list as shown, from top to bottom.
3.2.7 Setting the Time
Ensure that the PC time is correct before selecting this option. When selected the update is automatic,
setting the unit time to the PC’s time, with the following confirmation window:
or in the case of a communication failure
3.2.8 Pipe Scan
Allows configuration of the scanning of the CirrusPro 200DSC, and CirrusPro X4
The Pipe Scan menu should be set up when the unit is manufactured, based on the model type.
However, on scanning units, the number of pipes must be set to match the installation when not using
all four.
Another feature of this menu is the Pipe Hold function
that forces a scanning unit to sample from the selected
pipe. When a pipe is selected the next and all following
samples are from that pipe, pressing OK allows the
particle level to be monitored. A unit left in this state will
show the fault Pipe Scan Disabled.