Protec CIRRUS HYBRID User Manual Download Page 13

 

N93-601-00 Issue 1 

Page 13 of 25                        © Protec Fire Detection PLC 2015 

 

4.7 

Home Page 

Select the home icon 

 for quick navigation.  

 
Selecting a pipe dial on the home page displays the two fire 
and smoke technologies calculated to generate the combined 
fire and smoke signal (CFS). 
Fire and Smoke is a combination of the two technologies to 
create the combined fire and smoke (CFS) algorithm. 

 

 
 

Fire level dials 

 

 
 

Cloud 

Particles Per Cubic Centimetre (pcc) x 1000  
Scale 10,000 to 10,000,000pcc 
 

Optical 

Particles Percentage Obscuration Per Metre (%/m) 

 

 

Scale 0 

– 0.4%/m 

 
CFS  

Combined Fire and Smoke 

 

 

Mathematical algorithm 

 

 

Time zone 

Providing ‘timezone’ is enabled, the home page will display 

 to 

indicate the pipe night mode is activated. 

 

 

 
 
 

Silence and reset 

 
The Cirrus Hybrid is fitted with an internal buzzer. The buzzer will sound when the unit is in Fault, Pre-
alarm or Fire. 

Buzzer parameters 

Fault  

Slow 

1 second ON and 1 second OFF 

Pre Alarm  

Slow 

1 second ON and 1 second OFF 

Fire 

Fast 

½ second ON and ½ second OFF 

 

The user access level allows the internal buzzer to be silenced by pressing the silence button.  

 

When a fire is active the Cirrus Hybrid displays a reset button. Press the reset button to manually reset the 
fire. The fire will automatically reset once the potential hazard is removed.  

 

Reset button 

Summary of Contents for CIRRUS HYBRID

Page 1: ...ec Fire Detection plc Protec House Churchill Way Nelson Lancashire BB9 6RT ENGLAND 44 0 1282 717171 www protec co uk sales protec co uk PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS USER MAN...

Page 2: ...N93 601 00 Issue 1 Page 2 of 25 Protec Fire Detection PLC 2015 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15 11 15...

Page 3: ...16 4 11 Viewing the Network information 16 4 12 Viewing the Event log 17 4 13 Pipe Map 17 5 0 RESPONSE TO AN ALARM 18 5 1 Pre alarm 18 5 2 Fire 18 5 3 Silencing the Alarm 18 5 4 Resetting the Alarm 1...

Page 4: ...ctured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sen...

Page 5: ...tandard dictating aspirating smoke detector design practice EN54 parts 20 2 0 User Responsibilities The registered owner of the fire alarm system has specific responsibilities regarding the installati...

Page 6: ...ion water condenses onto the small particles and forms a cloud Consequently the thermally generated particles cause many droplets to form into the cloud which is then detected by the measuring system...

Page 7: ...e the hybrid system utilises the cloud chamber as the primary detector which is not affected by dust with a boost signal when the scatter chamber detects the smoke Using the two technologies allows th...

Page 8: ...ipe 4 B Air Exhaust Return C LCD Touch Display D LED Status Indication E Cable Entry Knock Outs F Cable Gland 20mm G Fire Protected Cable H Product Manufacture Label 4 0 Cirrus Hybrid General Componen...

Page 9: ...on 1 B2 SCD Location 2 B3 SCD Location 3 B4 SCD Location 4 C Terminal Connection Board D Earth block E Vacuum Pump Assembly F Water Bottle G Vacuum Silencer H Pipe Scanning Unit 1 I Cloud Chamber Asse...

Page 10: ...nts Key A Rear Display Cover Moulding B Label MAC address SCD Position C Front Display Assembly Securing Screws D Ribbon Cable to Terminal Board E Hinge Pin F Ribbon Cable to Cloud Chamber and Zone Sc...

Page 11: ...ted by the coloured markers The current status of fires and faults are shown under the Detector Status title bar below the dials For quick navigation there are a series of icons permanently displayed...

Page 12: ...correct for either user the following message will appear and the icon will change colour from the green to a red User Level Access Code default 1 4 4 2 If the code is incorrect the following message...

Page 13: ...4 m CFS Combined Fire and Smoke Mathematical algorithm Time zone Providing timezone is enabled the home page will display to indicate the pipe night mode is activated Silence and reset The Cirrus Hybr...

Page 14: ...and side Ensure you are logged in as user to edit the time Set the time either by the rotating the clock minute hand by selecting and dragging or using the symbols to increment decrement the hours min...

Page 15: ...quick navigation The airflow menu displays the current airflow for each pipe the fault tolerance monitoring for each pipe the airflow ignore box for each pipe the fan speed configurable from 5 to 100...

Page 16: ...cess level code can be changed to a custom number of digits ranging from 1 to 9 4 11 Viewing the Network information Click the network icon for quick navigation The network menu displays Protec Loop s...

Page 17: ...rid stores all fire faults and events in the event log The event log can store a maxium of 256 events In the user access level 16 latest events are viewable 4 13 Pipe Map Click the site pipe icon for...

Page 18: ...e Cirrus Hybrid unit will display the pipe text of the pipe in alarm and the fire alarm level 1 2 or 3 in the detector status list The fire alarm level LED will illuminate and the buzzer will pulse fa...

Page 19: ...ent airflow value At the time of commissioning when the pipe configurations are complete the airflow reading must be zeroed The Cirrus Hybrid sets the normalised zeroed value to 100 If the airflow rea...

Page 20: ...s means that the unit is not purging correctly User Action Contact a Protec operative or a Protec distributor 6 11 High Optical Background The optical analogue value has increased outside the operatio...

Page 21: ...e or a Protec distributor 6 18 Processor Fault The internal processor hardware has unexpectedly reset Cleared only on a full power cycle This is indicated if a problem has been detected with the micro...

Page 22: ...m the selected pipe While unit is in this state it will display a Pipe Scan Halted fault until the pipe hold function is disabled User Action Contact a Protec operative or a Protec distributor 6 25 He...

Page 23: ...creased above the stable background threshold Time Set The internal system time has been set Faults Cleared All system faults have been cleared system returned to normal status Event Log Cleared The e...

Page 24: ...d correct operation the system must be checked Daily by the User Every three months by Protec Fire Detection or an authorised representative Whenever building alterations have been performed which cou...

Page 25: ...n condensing ambient Indicators Power Green LED Fault Amber LED Pre Alarm Amber LED Alarm Fire Red LED 7 LCD touch screen display Water Requirements Distilled or Triple De Ionised Water replenished as...