Installer Guide

 The 

 Thermostat Backplate

To remove the thermostat backplate: 

Gently separate the display from the 
base by pulling from the center. 

R

C

AUX

DEHUM

HUM

W3

W2

W1/O/B

G

Y1

Y2

REMOTE/ OUTDOOR

DR

Y

CONT

ACT

To remove the thermostat

backplate from the wall: pry 

with screwdriver in either 

slot to remove back plate

24 VAC return

G  

Fan relay 

W1/O/B 

1st stage heat circuit 

 

or reversing valve

W2 

2nd stage heat circuit*

W3 

3rd stage heat circuit**

Y1 

1st stage compressor 

 

(Cool or Heat)

Y2 

2nd stage compressor 

 

(Cool or Heat)

C 

24 VAC common

AUX 

Ventilation Control  

HUM 

Humidifier control circuit 

DEHUM 

Dehumidifier control circuit

DRY 

FDD alerts, twist timer, etc. 

CONTACT
REMOTE
 

Remote sensor connections 

SENSOR
OUTDOOR
  Outdoor sensor connections 

SENSOR

IMPORTANT: This thermostat requires both R (24 VAC Return) and  

C (24 VAC Common) be connected to the backplate terminals.

*3rd stage heat for heat pumps with two compressor stages
**4th stage heat for heat pumps with two compressor stages

PSP4273_Installer man.indd   2

PSP4273_Installer man.indd   2

6/9/21   11:23 AM

6/9/21   11:23 AM

Summary of Contents for OEM PSP4273

Page 1: ...n Module Choose 7 Day 5 1 1 day or 1 Day Programming 365 Day Vacation Programming when connected to ProStat Web Portal Smart recovery auto adjusts Morning start time Setpoint Limiting Energy Watch tra...

Page 2: ...m at the main fuse panel Most residential systems have a separate breaker or switch for disconnecting power to the furnace Remove the cover of the old thermostat If it does not come off easily check f...

Page 3: ...rd stage heat circuit Y1 1st stage compressor Cool or Heat Y2 2nd stage compressor Cool or Heat C 24 VAC common AUX Ventilation Control HUM Humidifier controlcircuit DEHUM Dehumidifier control circuit...

Page 4: ...GAS is chosen the auxiliary heat will not be allowed to run during heat pump operation When ELEC is chosen up to two stages of auxiliary strip heat will be allowed to run For Heat Pump Only When the G...

Page 5: ...Electric Heat 5 Wire 1 Stage Cooling 1 Stage Heat 24VAC Power 24VAC Common 1st Stage Heat 1st Stage Cool Fan Residential Commercial 2 Stage Cooling with 3 stage Gas Heat 8 Wire 2 Stage Cooling 3 Stage...

Page 6: ...Stage Cooling 2 Stage Heat R 24VAC Power C 24VAC Common W1 O B Reversing Valve Y1 1st Stage Compressor Cool or Heat W2 Aux Heat G Fan Residential Commercial Heat Pump with O Reversing Valve 7 Wire 2...

Page 7: ...R 24V C 24V W1 O B Re W2 3rd W3 4th Y1 1st Co Y2 2nd Co G Fan Setup Step 31 Number of Co Residential Com O Reversing Val 6 Wire 1 Stage R 24 C 24 W1 O B Re Y1 1st C W2 Au G Fa Residential Commercial H...

Page 8: ...endar Days 0 720 Days 0 16 Set Service Filter Runtime Hours 0 1950 hours 0 17 Set Service Filter Calendar Days 0 720 Days 0 18 Set UV Lamp Calendar Days 0 720 Days 0 19 Set Humidifier Calendar Days 0...

Page 9: ...s Remote to Use list of wifi sensors currently first linked linked to thermostat This sensor in list step only appears if prior step Wireless Remote 49 Humidity Only With Heat On Off Off 50 Fan With H...

Page 10: ...y On Off Off 78 Dry Contact Polarity Open Closed Open 79 Dry Contact Use Condensate Vacation FDD Vacation 80 Humidity Polarity Open Closed Open 81 Dehumidify Polarity Open Closed Open 82 Dehumidify on...

Page 11: ...Calendar Days Setup Step 10 This counter displays the total number of calendar days that have elapsed since the counter was reset to help the user track filter usage Press FAN to reset Set Service Fi...

Page 12: ...that have elapsed since last reset to help the user track UV lamp runtime Press FAN to reset Set UV Lamp Calendar Days Setup Step 18 This timer allows the user to specify the number of calendar days t...

Page 13: ...0 12 00 DISPLAY Setpoint Limits Setup Step 22 When this feature is at any setting other than NO SETPOINT LIMITS the heat and cool setpoints can be restricted to preset levels set in steps 23 and 24 Th...

Page 14: ...ts on the thermostat display for non heat pump applications Number of Compressor Stages Setup Step 30 This feature is for heat pump applications only This feature allows the thermostat to control 1 or...

Page 15: ...heat will be used to stop running the heat pump and only run a fossil fuel source of heat NOTE Once the change to fossil fuel is made the heat demand must finish with fossil fuel Additional heat deman...

Page 16: ...utes after the second stage turns on before the third stage can turn on 0 60 Minutes Between 3rd and 4th Stage Setup Step 38 Specifies the minimum time in minutes after the third stage turns on before...

Page 17: ...e Stop Hour equal to the Start Hour will cause the fan to run 24 hours a day Fan Off Delay in Seconds Setup Step 64 This feature allows the user to increase the cooling or electric strip heating effic...

Page 18: ...etpoint should be entered by the user MANUAL or determined automatically by outdoor temperature AUTO An outdoor temperature sensor is required for the AUTO setting If the outdoor temperature sensor st...

Page 19: ...Aux Output Setup Step 67 Specifies which source will control the Aux output Choices are Time Uses the internal clock of the thermostat Temp Uses one of three temperature sources External The Auxiliar...

Page 20: ...ls Aux Output Trigger Point Temp Setup Step 74 Specifies the temperature from the above selected source above which the Aux Output is triggered A non adjustable two degree deadband is applied to avoid...

Page 21: ...Temps are adjustable from 40 to 80 Fahrenheit Dry Contact Operation Setup Steps 78 79 Dry Contact Polarity Setup Step 78 Open Normally Open The dry contact is open until the connected device closes th...

Page 22: ...thermostat may communicate and receive data from the ProStat web portal Local API Setup Step 84 Turning the local API to ON allows 3rd party software to interface with your thermostat such as a build...

Page 23: ...N ADR EVENT IS HAPPENING After setting your desired values for use during an ADR event the scrolling display will give a little information when an event is pending or active For instance when an ADR...

Page 24: ...ODE button While holding the MODE button press the WARMER and COOLER buttons together and the icon will appear on the display To unlock the keypad press and hold the MODE button While holding the MODE...

Page 25: ...this reset will be permanently lost 4 Factory Defaults 1 Press and hold SETUP for 10 seconds All icons will appear on the display Keep pressing the SETUP button until you see this screen 2 After all t...

Page 26: ...he thermostat View the jumper setting of J1 Gas Electric or Heat Pump J2 Reversing Valve RV O or RV B and J3 Fan Gas or Electric jumpers located on the back of the thermostat Remove thermostat from ba...

Page 27: ...and cycle down through the cooling stages Press WARMER to turn the cooling stages off Press MODE to exit 4 Press MODE until CALIBRATE SENSORS appears on the scrolling display Press WARMER for Yes or...

Page 28: ...attempt to turn on CAUSE The heating setpoint is set too low REMEDY Raise the heating setpoint or raise the heating setpoint limit See Setpoint Limits SYMPTOM When controlling a residential heat pump...

Page 29: ...ot apply to you For further information about this warranty contact Consumer Affairs at 877 254 4729 or by mail to 19001 Kermier Rd Waller Texas 77484 What Problems Does This Warranty Not Cover Goodma...

Page 30: ...TAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LOST PROFITS LOSS OF USE OF A CONTROL EXTRA UTILITY EXPENSES OR DAMAGES TO PROPERTY Some states and provinces do not allow the exclusion or li...

Page 31: ...les of the administering arbitration organization United States residents may choose the American Arbitration Association 1633 Broadway 10th Floor New York NY 10019 www adr org JAMS 1920 Main Street S...

Page 32: ...vation Science and Economic Development Canada ICES 003 Compliance Label CAN ICES 3 B NM8 3 B rev 2 06 09 2021 88 1475 P4273_Installer man indd 31 P4273_Installer man indd 31 6 9 21 11 23 A 6 9 21 11...

Reviews: