PS69-DPM ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 56 of 130
ProSoft Technology, Inc.
October 1, 2014
On the left side of the dialog set the focus to the slot number where the module is installed.
Set the focus to
"Other - Requires I/O Card Type ID"
from the available module types and
then double click on it.
2.4.2 Expansion General Configuration
The communications parameters for the module should be set as shown in the dialog below.
Expansion General Configuration
Value
Vendor
283
Product Type
12
Product Code
3
Series/Major Rev/Minor Rev
A
Input Words
44 + X (X = 0 ... 204)
Output Words
8 + Y (Y = 0... 240)
Extra Data Length
0
X = Number of Words configured for the Master module (PROFIBUS input data); input size can be in the range between 44 and 248
words
Y = Number of Words configured for the Master module (PROFIBUS output data); output size can be in the range between 8 and 248
words
Vendor ID / Product Type / Product Code for the PS69-DPM module are as shown
below:
o
Vendor ID: 283
o
Product Code: 12
o
Product Code: 3
Input Words: The input size must be at least 88 Bytes (44 Words). It must be large
enough to accommodate the status information required by the module, which is 88
Bytes (44 Words) plus the number of PROFIBUS input data. You can increase the size
of this area using the size of each Input module connected. The Input image starts with
byte 88.