PDPM ♦ ProLinx Gateway
PDPM Protocol Configuration
PROFIBUS DP Master
Protocol Manual
ProSoft Technology, Inc.
Page 43 of 70
June 24, 2013
4
PDPM Protocol Configuration
In This Chapter
[PROFIBUS Master] .............................................................................. 43
[PROFIBUS Master Commands] ........................................................... 45
The following is excerpted from a configuration file showing typical examples of
the PROFIBUS Master Port and PROFIBUS Master Command sections of a
CFG file for a PDPM port. Shipped with each unit (or available from the web) is a
default configuration file that can easily form the basis for a working solution. This
file can either be downloaded from the ProSoft web site at
www.prosoft-technology.com, or transferred from the module.
# This is the data area for setting the Profibus Master parameters
[Profibus Master]
Swap Input Bytes : No #Swap bytes in input image (yes or no)
Swap Output Bytes : No #Swap bytes in output image (yes or no)
Comm Failure Mode : 1 #0=x-fer on comm fail, 1=no x-fer on fail
Watchdog Register : 1000 #DB register to monitor for change (-
1=watchdog not used)
Watchdog Timeout : 50 #.1 second intervals for watchdog timeout
Watchdog Reset Value : 255 #Value to set Profibus outputs to on timeout
condition
# This section contains the Profibus Master commands to be processed by the
# module.
[Profibus Master Commands]
# Database Register Poll Command Data
# Enabled Address Count Interval Node Code Length
START
1 600 10 0 3 66 32
1 610 7 0 4 66 32
2 620 0 10 3 254 2
2 0 0 1200 0 254 0
END
4.1
[PROFIBUS Master]
# This is the data area for setting the Profibus Master parameters
[Profibus Master]
Swap Input Bytes : No #Swap bytes in input image (yes or no)
Swap Output Bytes : No #Swap bytes in output image (yes or no)
Comm Failure Mode : 1 #0=x-fer on comm fail, 1=no x-fer on fail
Watchdog Register : 1000 #DB register to monitor for change