Checking Write Data
The following steps show you how to verify that the WriteData Command is
working.
1
In RSLogix, navigate to the processor controller tags
MNETC.DATA.W
RITE
D
ATA
[0]
through
MNETC.DATA.W
RITE
D
ATA
[9]
.
2
For words
[0]
through
[9],
enter the numbers shown in the following
illustration.
This action sends the values you entered to the
M
ODBUS
C
LIENT
0
on the
MVI56E-MNETC, and then to the Quantum processor, where you will be able
to see the data in Concept.
3
In Concept, navigate to the
R
EFERENCE
D
ATA
E
DITOR
to monitor the
processor memory addresses from 400401 through 400410. The data should
match the data you sent from RSLogix 5000.