MVI71-DNPSNET
♦
PLC Platform
Reference
Distributed Network Protocol Interface Module
Page 68 of 100
ProSoft Technology, Inc.
September 22, 2008
[Section]/Item Value
Range
Description
Class 2 Unsol Resp Min:
1 to 255
events
Minimum number of events in Class 2
required before an unsolicited response will
be generated.
Class 3 Unsol Resp Min:
1 to 255
events
Minimum number of events in Class 3
required before an unsolicited response will
be generated.
Unsol Resp Delay:
0 to 65535
milliseconds
Maximum number of 1 millisecond intervals
to wait after an event occurs before sending
an unsolicited response message. If set to
0, only use minimum number of events.
Uresp Master Address:
0 to 65534
DNP destination address where unsolicited
response messages are sent.
AI Events with time:
Y or N
This parameter sets if the analog input
events generated by the module will include
the date and time of the event. If the
parameter is set to N, the default is set to no
time data. If the parameter is set to Y, the
default object will include the time of the
event.
Time Sync Before Events:
Y or N
This parameter determines if events are to
be generated by the module before the time
synchronization from the master unit. If the
parameter is set to N, events will be
generated irrespective of the module's time
sync status. If the parameter is set to Y,
events will be generated only if the module's
time is synchronized.
[Section]/Item Value
Range
Description
[DNP ENET IP Addresses]
List of valid IP addresses accepted by
module
START
# Insert the list of IP addresses for the host(s) to connect to this unit. Only used if Use IP List set to
1.
END