Reference MVI71-DNPSNET
♦
PLC Platform
Distributed Network Protocol Interface Module
ProSoft Technology, Inc.
Page 55 of 100
September 22, 2008
Block 9958 or 258 - PLC Binary Input Event
If the PLC sends a block 9958, the module will place the binary input event data
in the block into the event buffer and alter the data values for the points in the
DNP binary input database. The format for the event message is shown in the
following table.
Word Offset in
Block
Data Field(s)
Description
0
Block ID
This field contains the value of 9958 identifying the event
block to the module.
1
Event Count
This field contains the number of events contained in the
block. Valid values for this field are 1 to 12.
2
Sequence Counter
This field holds the sequence counter for each 9958
block transfer. This synchronizes and confirms receipt of
the block by the module.
3
DNP Binary Input
Data point
This is the data point in the DNP binary input database
represented by the event.
4
Month/Day/State
Formatted: bits 0 to 4 = Day, bits 8 to 11 = Month, bit 15
= digital state for point. All other bits are ignored.
5 Hour/Minute
Formatted: bits 0 to 5 = Minutes, bits 8 to 12 = Hour. All
other bits are ignored.
6
Sec/Millisecond
Formatted: bits 0 to 9 = Milliseconds, bits 10 to 15 =
Seconds.
7
Year
This is the four digit year for the event.
8 to 12
Five words of data for Event #2.
13 to 17
Five words of data for Event #3.
18 to 22
Five words of data for Event #4.
23 to 27
Five words of data for Event #5.
28 to 32
Five words of data for Event #6.
33 to 37
Five words of data for Event #7.
38 to 42
Five words of data for Event #8.
43 to 47
Five words of data for Event #9.
48 to 52
Five words of data for Event #10.
53 to 57
Five words of data for Event #11.
58 to 62
Five words of data for Event #12.
63
Spare
Not Used
Up to 12 events can be passed from the PLC to the module in each block. To
ensure that the block reached the module and was processed, the module will
send a response read block 9958 to the PLC. The format of the block is shown in
the following table.
Word Offset in
Block
Data Field(s)
Description
0
Block ID
Identification code for block set to 9958.
1
Block ID
Block identification code for request from PLC by the
module.
2
Event Count
This field contains the number of events processed by
the module.