The parameters displayed have the following definitions:
Rx Count
- Number of messages received on UDP socket
Tx Count
- Number of messages transmitted on UDP socket
Tx State
- 0=not transmitting, 1=transmitting
TCP State
- Value used for UDP/IP socket state machine
Busy Flag
- 0=not busy, 1=TCP has control of DNP server, 2=UDP has control
of DNP server, 3=Unsolicited message being sent
App Frame
- 0=no application data frame data, 1=application data available
Tx Frame
- 0=Data link level frame ready to send, 1=Data link level message not
ready to send
Packet Length
- Length of message left to process
4.1.7 Database
View
Menu
Press
[D]
from the Main Menu to open the Database View menu. Use this menu
command to view the current contents of the module's database. Press
[?]
to
view a list of commands available on this menu.
Viewing Register Pages
To view sets of register pages, use the keys described below:
Command Description
[0]
Display registers 0 to 99
[1]
Display registers 1000 to 1099
[2]
Display registers 2000 to 2099
And so on. The total number of register pages available to view depends on your
module's configuration.