5.4.2 Studio 5000 Adjustment (Optional)
This (optional) section allows you to tailor the ILX69-PBM input/output sizes to conserve
memory space in
the CompactLogix™ processor.
Module Properties
1
With the CompactLogix controller in
Offline
mode, double-click on the
M
ODULE
PBM
in the
I/O Configuration
dialog to open the
Module Properties
.
2
In the
Module Properties
dialog, edit the
Connection Parameters
I
NPUT
S
IZE
to the
sum of PROFIBUS Input
words
+ 44.
In the example, there are 8 PROFIBUS input bytes, or (4) 16-bit words: 4 + 44 =
48
.
For outputs, edit the
Connection Parameters
O
UTPUT
S
IZE
to the sum of PROFIBUS
Output
words
+ 8.
In the example, there are 8 PROFIBUS output bytes, or (4) 16-bit words: 4 + 8 =
12
.
3
Click
A
PPLY
, then
OK
.