Language Settings:
Press MENU button and select “Language Setting” step to change the language. A new menu
will be displayed including time and language options:
Use UP, DOWN and MENU buttons to select language. Only Turkish and English languages
are available. Once completed press EXIT button to return to settings screen.
Prosense Panel Monitor Software Option
Prosense S-DP8 Control Panel has an optional RS485 module and connections on main
board. Prosense S-DP8 Control panel with firmware version V3.02 can communicate to
Prosense Panel Monitor Software control program via RS485 module. S-DP8 panel with
V3.01 firmware version needs hardware upgrade to enable RS485 module.
Important
: The date and time information will be unavailable once RS485 module installed.
What to Do In Case of Alarm
There are 3 independent LEDs for each detector as fault, alarm and power LEDs. In addition
to them there are two alarms, one fault, one power and one battery LED used to monitor
overall panel status. ALARM1 and ALARM2 LEDs will be activated and kept active when any
of the detectors raised an alarm. The LEDs and related relay outputs will be active until
detector changes the alarm status and alarms acknowledged by user.
Checking Alarm and Fault Functions
The main board has 4 test buttons on top of each relay to generate false alarm and test relay
function. Relay functions can be tested by pressing to test buttons after completing cabling.
The relay will be activated while pressed the test button and deactivated when button
released.
Important:
Test buttons do not provide functionality to check that the control unit will
actually react at a specific gas concentration. This can only be achieved by applying a
calibration gas on the detector.
Please refer to the mandatory safety procedures (gas alarm) set forth by your safety
manager in case of any alarm. Always keep calm and follow these instructions:
1.
Put out all naked flames (including cigarettes, pipes, etc.)
2.
Turn off all gas appliances.
Language
Turkish
English