![ProMinent ProMix C Operating Instructions Manual Download Page 21](http://html1.mh-extra.com/html/prominent/promix-c/promix-c_operating-instructions-manual_1616984021.webp)
Pr
o
Minent ProMix
‘S & C’ Polymer Feeder
ProMix Series S&C User Manual
Press
ENTER
@
Polymer
to view or adjust the
Fill Time
,
Flush time
or
Wait for Flow
time.
All three times are adjusted in the same way.
In this
example we’ll press
ENTER
@
Fill Time
.
Key
RIGHT
to move the cursor &
UP
or
DOWN
to change the digit.
Key
EXIT
to abandon or
ENTER
to execute.
Displays new, adjusted
Fill Time
.
Press
EXIT
to return to main menu.
If you
ENTER
a time less than 1 second,
the
Fill Time
will be set to 1 second.
If you
ENTER
a time greater than 60 seconds,
the
Fill Time
will be set to 60 seconds.
Sidebar:
Fill Time:
Minimum = 1 second, Maximum = 60 seconds.
Factory default = 30 seconds.
Flush Time:
Minimum = 1 second, Maximum = 300
seconds.
Factory default = 60 seconds.
Wait for Flow:
Minimum = 1 second, Maximum = 30
seconds.
Factory default = 5 seconds.
Summary of Contents for ProMix C
Page 50: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual B 2 Control Panel Drawings...
Page 51: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 52: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 53: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 54: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Page 55: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...