Name
No.
Type
Description
Metering
monitor
19
BYTE
If a metering monitor is installed, it can be switched on (1).
Deactivation is (0).
Concentra‐
tion
20
FLOAT
If the concentration calculation is activated on the pump, the
current concentration can be read off here (delta
®
only).
Error
21
UINT16
bit
Name
Function
0
Minimum
Metering liquid level too low
1
Batch
Too many metering strokes >
100000
2
Analogue current is less than
4 mA
3
Analogue >
23mA
Analogue current is greater
than 23 mA
4
Metering
monitor
Metering monitor fault
5
Diaphragm
rupture
Faulty diaphragm in the
dosing head
6
Airlock
Air in the dosing head (delta
®
only)
7
Overpressure Overpressure in the
hydraulic system
8
-
-
9
-
-
10
Low pressure Pressure too low in the
hydraulic system (delta
®
only)
11
Stroke length
changes
The stroke length was
changed in locked state.
12
Bleeding
Automatic bleeding is not
possible (delta
®
only)
13
Bus error
Bus error reported by the
module
14
System error System components faulty -
see LCD screen
15
Module error Fault in module handling
Warnings
22
UINT16
bit
Name
Function
0
Minimum
Metering liquid level too low
1
Calibration
Stroke length set outside the
calibration tolerance
2
Metering
monitor
Metering monitor fault
3
Diaphragm
rupture
Faulty diaphragm in the
dosing head
4
Airlock
Air in the dosing head
5
-
-
6
-
-
Operation