Mounting and installation
IMPORTANT
•
The place of installation must be dry and protected against freezing and must
guarantee that the UV disinfection system is protected against chemicals, dyes, and
vapours.
•
The ambient temperature as well as the radiation temperature close-by may not
exceed 40
°
C.
•
If solid particles or clouding agents are present in the water to be disinfected, a
suitable filter is to be installed upstream of the disinfection system!
•
Make sure that the maximum permissible operating pressure stated in the enclosed
datasheet is not exceeded!
NOTE
Despite the use of sophisticated lamp ballasts with gentle lamp ignition, the UV
disinfection system is to be operated such that frequent switching on and off of the UV
lamps is avoided.
5.1
Radiation chamber
The type of the radiation chamber is described in the enclose datasheet.
Type “vertical wall-mounting”, type “horizontal” or type “upright”.
5.1.1
Mounting
IMPORTANT
•
Only the type of mounting listed in the enclosed datasheet is permissible.
•
Leave sufficient space for maintenance work!
The required clearance is described in the enclosed datasheet!
Vertical wall-mounting
왘
Install the radiation chamber vertically on the wall or a suitable frame using the enclosed
mounting material
Horizontal
왘
Install the radiation chamber horizontally on the wall or a suitable frame using the enclosed
mounting material
Upright
왘
Position the radiation chamber upright on the floor
5.1.2
Fixing of the danger sign
NOTE
The enclosed self-adhesive danger sign is to be affixed well-visibly at the radiation
chamber.
5.1.3
Connections, hydraulic
WARNING
For applications with high disinfection demands (e.g. drinking water disinfection) without
planned interruption of the water flow in cases of failures (e.g. switching off of delivery
pump): Install an automatic shut-off valve downstream of the radiation chamber and
connect it to the control!
The automatic shut-off valve must close automatically such that the water flow is
interrupted even in case of a possible failure of the supply voltage.
BA_DS_011_02_07_GB.p65
12.02.2007, 12:03 Uhr
8