Troubleshooting
Possible cause
UV C sensor faulty
Remedy
왘
Install new UV C sensor
Possible cause
Ballast faulty
Remedy
왘
Install new ballast
UV C sensor cannot be calibrated
w/m
2
Message: Flashing down arrows
Possible cause
UV lamp faulty
Remedy
왘
Install new UV lamp
Possible cause
UV C sensor faulty
Remedy
왘
Install new UV C sensor
Possible cause
Ballast faulty
Remedy
왘
Install new ballast
UV C sensor cannot be calibrated
Control does not respond to the CALIBRATION key
Possible cause
System was switched on less than 1 minute ago
Remedy
왘
wait until 1 minute has expired
Possible cause
UV C sensor signal is smaller than 50% and the system was switched on more than
5 minutes ago
Remedy
왘
Perform a preliminary calibration as described in 6.3
Insufficient lamp current
XXX w/m
2
12345h
12345
55
50
Message: Three flashing X
Insufficient lamp current
Message: Flashing display
Possible cause
Lamp cable or UV lamp faulty
Remedy
왘
Inspect connections, replace cable and/or UV lamp, if necessary
Acknowledge the error by pressing the ENTER key and interrupt the supply voltage and
switch on again.
Shut-off valve does not open
Possible cause
Fusible link blown
Remedy
왘
Open control (see 5.2.3) and examine fusible link F2
왘
Check the valve before installing a new fusible link (2.5A slow)