Page 38
7.7
Troubleshooting
CAUTION!
• Only authorised electricians are permitted to perform troubleshooting operations on the
opened control cabinet and replace components!
Warning threshold undershot
Indication: Arrow pointing down
Safety threshold undershot
Indication: Two flashing arrows pointing down
The remaining clear flushing time is shown
(2 squares flash instead of the seconds)
Fault: Safety threshold undershot (after maximum clear flushing time has elapsed)
Error message: UV sensor
➤
Confirm error message with ENTER key
➤
Press CHANGE key to assume emergency mode (see 4.3.20)
Emergency mode: Safety threshold undershot
➤
System continues operating in emergency mode
Possible cause
Coating on lamp protective tube
Remedy
➤
Clean lamp protective tube
Possible cause
Deterioration of UV transmission of water to be treated
Remedy
➤
Improve water quality
Possible cause
UV lamp at end of useful life
Remedy
➤
Install new UV lamps
Possible cause
Incorrect lamp current
Remedy
➤
Operate with standard current
Possible cause
Sensor not calibrated correctly
Remedy
➤
Recalibrate sensor
Fault: Lamp failed
Error message: xx lamp defective
➤
Confirm error message with ENTER key
➤
Press CHANGE key to assume emergency mode (see 4.3.20)
Emergency mode: Lamp failed
➤
System continues operating in emergency mode
Possible cause
Lamp xx defective
Remedy
➤
Install new UV lamps
Possible cause
Incorrect lamp current
Remedy
➤
Operate with standard current
Possible cause
Ballast defective
Remedy
➤
Replace ballast
IMPORTANT!
• The number of failed UV lamps is indicated.
• If more than one UV lamp has failed, the individual lamps can be queried by pressing the
UP and DOWN key.
Emergency mode
UV sensor
Fault
xx lamps defective
Lamp #xx
Emergency mode
xx lamps defective
Lamp #xx
Maintenance
↓
↓
↓
↓
↓
55.0 W/m
2
10 h
Operation
20
ON/OFF
↓
↓
↓
↓
↓
↓
↓
↓
↓
↓
40.0 W/m
2
Clear flushing
Time 00:11
Fault
UV sensor