DCM 2 Installation
Page
34
Time
Modulation
Not applicable
Pump ON time reduced as sensor
approaches TurnOFF setpoint.
Pump Type
Selection
User selects Pump Type which sets default
mL/stroke & Max. SPM..
‘Other’ type allow user to set MAX SPM.
All types allow user to modify mL/stroke.
Checks that existing feed rates are possible
when user changes pumps or set to MAX
SPM and alarm message if feed rate
modified.
Pump changes update the event log.
Not applicable
Relay & Frequency Controls Comparison (cont.)
Notes
1.
Contact Sets
Runs once per controlling contact closure.
In addition to being able to use Contact sets to turn ON & OFF relays and frequency
controls, contact sets can have the following compensation:
Invert ON/OFF:
Switches the logical sense of the contact set so you can control on contacts opening or
closing.
Applications: Allows a control only when relay changes state
Surge tank fill, remote disable, second flow switch
2.
Feed Limits
Users may set
OFF on Alarm
, turning OFF a Relay or Frequency on a time limit.
6.7. System Alarms & Indicating LEDs
System Alarms
Alarms are not specific to any sensor or control.
Name
Alarm Message & Cause
Effect
12VDC External
“
Low Alarm
”
Wiring errors or a fault on any sensor
powered by the controller 12VDC
‘DC Power Output’ supply
Correct wiring. Remove defective sensor.
12VDC thermal fuse auto-recovers.
While alarmed: sensors, meters and current loops
powered by the 12VDC supply will not operate.
Internal 2.5V
“
Out of Range
”
Sensor, meter or contact set wiring
error
Used to auto-calibrate all sensor measurements to
remove power supply drift error.
All sensor measurements stop auto-calibration.
Indicating LEDs
Name
Location
Function
Blue
‘OK’
Facepanel to left of LCD
Screen
On when there are no Alarms
Flashes when flow switch is OFF or in Flow ON Delay
Red
‘ALARM’
Facepanel to left of LCD
Screen
Flashes when any alarms are active.
Green
‘LINK’
Top Left of Ethernet jack
On steady with Ehternet connected
Green
Top Right of Ethernet jack
Flashes with Ethernet activity
Summary of Contents for DCM 2 Series
Page 2: ...DCM 2 Installation Page 2 This page intentionally left blank ...
Page 19: ...DCM 2 Installation Page 19 ...
Page 20: ...DCM 2 Installation Page 20 DCM2 safety interlock connections for vacuum filter systems ...
Page 21: ...DCM 2 Installation Page 21 DCM2 safety interlock connections for pressure filter systems ...
Page 23: ...DCM 2 Installation Page 23 DCM2 Cl pH CLB3 Free Cl2 Sensor Connections ...