4. Password Security
4.1. Overview
DCM2 controllers use 4 levels of password for controller access and to stamp the activity log:
Public, Operator, Configuration, and Administrator
Refer to Section 4.2 for default user IDs and passwords.
Passwords are defaulted OFF for keypad users and ON for Browser users.
Passwords cannot be turned OFF for Browser users.
There are 7 user assignable passwords which are distributed between Operators & those allowed to Configure.
Passwords are a maximum of 9 letters and numbers and are case sensitive. The controller blocks the use of
HTML delimiter characters by limiting password content to letters and numbers only.
The controller blocks duplicate passwords.
4.2. Password Level Activities
Password Level
Activities
Notes
Public
1 per DCM2
Views current state and alarm log.
Cannot adjust or edit.
Password not required for keypad or
browser use. Browser access to controller
alarm log only.
Operator
4 per DCM2
Operator1 - 4
Calibrate sensors. Prime Pumps or
force them off.
Changes setpoints and feed rates.
Can view but not edit all controller
configure level settings
Can edit own user ID & password.
Keypad users, password only editing.
Controller default user ID is
Operator1
thru
Operator4
with default passwords 1..4.
Configure
3 per DCM2
Configure 5 - 7
Configure controls, interlocks and
blocking.
Sets sensor compensation, feed
alarms & limits.
Sets Event Timers, blocking & cycle
days.
Zeroes water meters
All Operator Activities
Can edit own user ID & password.
Keypad users, password only editing.
Controller default user ID is
Configure5
thru
Configure7
with default passwords 5..7.
Administrator
1 per DCM2
Set IP address and network
parameters.
All Operator & Configure Activities
Browser: Can define other users as
Operator
or
Configure
Cannot view other users passwords.
Can edit own password, default ‘AAAA’
Cannot edit ‘Admin’ user id
Summary of Contents for DCM 2 Series
Page 2: ...DCM 2 Installation Page 2 This page intentionally left blank ...
Page 19: ...DCM 2 Installation Page 19 ...
Page 20: ...DCM 2 Installation Page 20 DCM2 safety interlock connections for vacuum filter systems ...
Page 21: ...DCM 2 Installation Page 21 DCM2 safety interlock connections for pressure filter systems ...
Page 23: ...DCM 2 Installation Page 23 DCM2 Cl pH CLB3 Free Cl2 Sensor Connections ...