ENG
31
Service settings manual
Heating system:
Setting range:
floor heating
0,2 - 0,8
wall heating
0,6 - 1,0
radiator heating
0,8 - 1,4
With adjusting the heat curve steepness, the controller is tuned with the
building. For optimal controller operation, the right setting of the heat
curve steepness is very important.
Preferred settings of the heating curve steepness:
Diagram of heat curves
Outdoor temperature [°C]
St
and-p
ip
e t
emperat
ur
e [
°C]
20
30
40
50
60
70
80
90
100
-20
-15
-10
-5
0
5
10
15
20
S=0,4
Tvmax
Tvmin
Tkmin
S=0,6
S=0,8
S=1,0
S=1,2
S=1,4
S=1,6
S=1,8
S=2,0
S=2,2
S=0,2