background image

1. GENERAL INFORMATION 

Attention

: All users must read these operating 

instructions carefully prior to the initial operation. These 
instructions are intended to acquaint the user with the 
hoist controller and enable him/her to use it to the full 
extent of its intended capabilities. 

The operating instructions contain important information  
on how to handle the hoist controller in a safe, correct and 
economic way. Acting in accordance with these 
instructions helps to avoid dangers, reduce repair costs 

and downtime and to increase the reliability and lifetime of 
the hoist controller. 
Anyone involved in doing any of the following work with 
the hoist controller must read the operating instructions 

and act accordingly: 

• Operation, including preparation, trouble shooting and 

cleaning 

• Maintenance, inspection, repair 

• Transport 

Apart from the operating instructions and the accident 
prevention act valid for the respective country and area 

where the hoist controller is used, also the commonly 
accepted regulations for safe and professional work must 
be adhered to. 
The user is responsible for the proper and professional 

instruction of the operating personnel. 

Suitable for entertainment use 

The 

PRO

LYFT AETOS hoist controllers are specially 

designed for use in the Entertainment industry. They must 
only control electric chain hoists that are suitable for use 
in the Entertainment industry. 

Combining the hoist controller with different type of 
electric chain hoists might lead to unwanted, unexpected 
or dangerous situations. 
The 

PRO

LYFT AETOS hoist controllers are not designed 

to control hoists suspending or lifting loads above people. 

Read the manual of the electric chain hoists before 
starting to operate them with the hoist controller. 

Regulations 

The accident prevention act and/or safety regulations of 
the respective country for using manual and electric chain 
hoists must be strictly adhered: 

• Europe:  

• Machine Directive 2006/42/EG 
• Safety of Machinery NEN 12100:2010 
• Germany: BGV D6, BGV D8 

Additional regulations are in effect for lifting or suspending 
loads over people. 
Germany: SQ P2 
The Netherlands: NPR8020-10 

United Kingd

om: BS7950-1

 

Maintenance/Repair 

In order to ensure correct operation, not only the 

operating instructions, but also the conditions for 
inspection and maintenance must be complied with.  If 
defects are found or abnormal  noise is to be heard stop 

using the hoist controller immediately. 

Attention:  

Before  starting to work  on  electrical 

components  the  power-supply is to be cut off. 

2. INCORRECT OPERATION 

Do not 

exceed the rated power capacity per controlled 

channel. 

Do not

 lift stuck or jammed  loads. 

Do not

 shortly and frequently actuate the up/down 

switch. 

• Do not 

control hoists if the movement of the load is not 

visible from the operating position. 

• Do not

 control hoists if you are skilled for lifting loads 

• Do not 

use cables with damaged strain reliefs and/or 

isolation. 

• Do not 

use any input- or output cables that are not 

suitable for the supplied voltage and / or current. 

• Do not

 use the Thuja data connection (link in, link out) 

with other network devices unless these devices are 
specified to be suitable for use in the Thuja data 
network. 

• Do not 

connect the controller to a mains connection that 

is not properly fused. 

• Do not 

use the controller without proper grounding. 

• Do not

 connect more then one hoist on a single 

channel.

 

3. ELECTRIC CONNECTIONS 

All electric connections must be used with respect for the 
specified voltages and maximum power consumption. 

Power input: 

The power input connector is a 5pin CEEform connector 
suitable for 3 phase 32Amp / 400Volt. 3 Phases, neutral 
and ground. 

Depending on the type of controller it can be plugged in to 
either a 3 phase 400V or a 3 phase 230V mains 
connections. 

Make sure the mains connection is fused at maximum 
32Amps per phase. It is advised to use circuit breakers  
with a C or D characteristic. 

Make sure the mains connection is properly grounded. 
Improper grousing might lead to dangerous with the 

risk 

of electric shock. 

Maximum power consumption per hoist. 

Each hoist channel is capable of switching an electric 
chain hoist with maximum power consumption of 1,5kW. 

 

Power output to the hoists 

For each 4 hoist channels there is a Harting 16 output 
connector.  

Make sure the cables (and each individual wire of the 
cable) connected to the output connector are suitable for 
minimum 10Amps at 400V per wire.  

To avoid voltage drops longer cables should have bigger 
wire diameters. 

 page 

!

4

AETOS 

Range

AETOS 

Range 

 

21

Part nr.

Catalogue code
PAE-250DC

Description

1

PAE-S-671387

GEAR ASSY AETOS 250

2

PAE-S-671383

MOTOR SPACER AETOS 250

3

PAE-S-BC250-01C

BRAKECOVER AETOS 250 COMPLETE

4

PAE-S-MC250-01C

MOTORCOVER AETOS 250 COMPLETE

5

PAE-S-671375

MOTOR ASSY 400-230V 3PH 50-60HZ AETOS 
250

6

PAE-S-671454

CONTROL BOARD DC AETOS 250

7

PAE-S-671503

TRANSFORMER BOARD PRI. 400-230V 
SEC.24V

8

PAE-S-671258

LIMIT SWITCH DETECTION 207-400VOLT

9

PAE-S-671195

CONTROL BOARD RETAINER

10

PAE-S-671396

BRAKE BFK457-04 AETOS 250

11

PAE-S-671385

GASKET MOTOR SPACER AETOS 250

12

PAE-S-670994

CHAIN GUIDE TOP AETOS 250

13

PAE-S-670993

CHAIN GUIDE BOTTOM AETOS 250

14

PAE-S-671393

MICRO SWITCH ASSY AETOS 250

15

PAE-S-671426

LIMIT SWITCH ADAPTER AETOS 250

16

PAE-S-671429

DISENTANGLE PLATE AETOS 250

17

PAE-S-671428

DISENTANGLE PLATE INSERT AETOS 250

18

PAE-S-671112

ANCHOR COVER PLATE AETOS 250

19

PAE-S-671052

CLUTCH HUB ASSY AETOS 250

20

PAE-S-9120060

DISC SPRING 28x14,2x0,8 AETOS 250

Part nr.

Catalogue code
PAE-250DC

Description

21

PAE-S-671041

SPACER BUSH 18x14x10 AETOS 250

22

PAE-S-780537

SEALING DISC FOR M20

23

PAE-S-671145

CABLE GLAND WITH ANTIKINK FITTING

25

PAE-S-671216

ASSEMBLED CONTROL LINE AETOS 250-
500-1000

26

PAE-S-671416

O-RING M20

27

PAE-S-671415

BLIND SCREW PLUG M20X1,5

28

PLS-033050011

PLASTIC RING 5Xd 5,3X25X2,5,PL

29

PLT-10-010

TAG LRP125 RFIP,25MM FOR HOIST

30

PAE-S-671380

SUSPENSION HOOK ASSY AETOS 250

31

PAE-S-671036

LOAD PIN AETOS 250

32

PAE-S-9123049

RETAINING RING DIN6799-10-FST

33

PAE-S-9129031

RETAINING RING DIN471-8x0,8

34

PAE-S-9131099

KEY 2x2x14 DIN6885-A

35

PAE-S-9102332

BOLT M5X20 INBUS 8.8 DIN7984

36

PAE-S-9102194

BOLT M5X25 INBUS 8.8 DIN7984

37

PAE-S-9102199

BOLT M5X16 INBUS 8.8 ISO4762

38

PAE-S-9102319

BOLT M3X10 INBUS 8.8 ISO4762

39

PAE-S-9121029

WASHER 3,2X7X,0,5 FLAT ISO7090

40

PAE-S-9104131

BOLT M3X8 INBUS 8.8 C.SUNK ISO10642

41

PAE-S-671459

CONTROL BOARD MOUNTING BRACKET 
AETOS 250

12. SPARE PARTS: Aetos 250 Direct Control

Summary of Contents for PRO LYFT AETOS PAE-1000DC Series

Page 1: ...ection and maintenance must be complied with If defects are found or abnormal noise is to be heard stop using the hoist controller immediately Attention Before starting to work on electrical component...

Page 2: ...ric connections must be used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt...

Page 3: ...c connections must be used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt 3...

Page 4: ...eatures y engineered product attributes The AETOS range comprises of a 0kg and 1000kg hoist and will be expanded in the near future ProLyft Program ains a unique service programme on its complete hois...

Page 5: ...e taken at a distance of 1 m from the hoist at 9 positions in accordance with DIN 45635 precision class 2 2 CORRECT OPERATION Lifting capacity The PROLYFT electric chain hoist series AETOS has been de...

Page 6: ...is due to its position gathering water when the hoist is used in the rain The bottom of the cabinet is equipped with drain holes Drain holes must be checked regularly to avoid them from being blocked...

Page 7: ...s of two pins Make sure that the load hook irrespective of the reeving is always positioned vertically under the WWW PROLYTE COM Fig 5 Fig 6 Fig 7 Fig 8 swiveling hook suspension see Fig 9 On single s...

Page 8: ...female to connect a pendant control This pendant control will either close the circuit inside the hoist for lifting when the UP button is pressed or the circuit inside the hoist for lowering when the...

Page 9: ...imum 10Amps at 400V per wire To avoid voltage drops longer cables should have bigger wire diameters page 4 AETOS Range AETOS Range 9 10 WWW PROLYTE COM INTRODUCING THE PROLYFT AETOS RANGE When Simplic...

Page 10: ...wer consumption per hoist Each hoist channel is capable of switching an electric chain hoist with maximum power consumption of 1 5kW Power output to the hoists For each 4 hoist channels there is a Har...

Page 11: ...e or independently operate the hoist must have had suitable training and be competent Operators are to be specifically nominated by the company and must be familiar with all relevant safety regulation...

Page 12: ...ith respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt 3 Phases neutral and ground De...

Page 13: ...etwork devices unless these devices are specified to be suitable for use in the Thuja data network Do not connect the controller to a mains connection that is not properly fused Do not use the control...

Page 14: ...dipping chain in caustic solvents Also avoid surface treatments that can hide cracks and flaws or other surface damage The chain must be lubricated in a no load condition so that lubricant can enter...

Page 15: ...d disconnect it from the hoist and re thread it correctly In some cases it may be necessary to remove the last link Before initial operation lubricate the unloaded chain and test all hoist functions u...

Page 16: ...nch acc to DIN 3116 in anti clockwise direction until blocked Attention The adjusting nut is secured with a screw securing agent Loctite 243 For loosening it may be necessary to heat up the area of th...

Page 17: ...tions in general Check all nuts screws and locking devices for tightness Chain container Ensure the chain container is securely fastened Check for cracks or wear Suspension bolt Connection between hoi...

Page 18: ...it can be plugged in to either a 3 phase 400V or a 3 phase 230V mains connections Make sure the mains connection is fused at maximum 32Amps per phase It is advised to use circuit breakers with a C or...

Page 19: ...channel is capable of switching an electric chain hoist with maximum power consumption of 1 5kW Power output to the hoists For each 4 hoist channels there is a Harting 16 output connector Make sure t...

Page 20: ...controller immediately Attention Before starting to work on electrical components the power supply is to be cut off 2 INCORRECT OPERATION Do not exceed the rated power capacity per controlled channel...

Page 21: ...suitable for use in the Thuja data network Do not connect the controller to a mains connection that is not properly fused Do not use the controller without proper grounding Do not connect more then on...

Page 22: ...itable for use in the Thuja data network Do not connect the controller to a mains connection that is not properly fused Do not use the controller without proper grounding Do not connect more then one...

Page 23: ...ns must be used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt 3 Phases neut...

Page 24: ...IONS All electric connections must be used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase...

Page 25: ...used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt 3 Phases neutral and gr...

Page 26: ...be used with respect for the specified voltages and maximum power consumption Power input The power input connector is a 5pin CEEform connector suitable for 3 phase 32Amp 400Volt 3 Phases neutral and...

Page 27: ...with damaged strain reliefs and or isolation Do not use any input or output cables that are not suitable for the supplied voltage and or current Do not use the Thuja data connection link in link out w...

Page 28: ...onditions for inspection and maintenance must be complied with If defects are found or abnormal noise is to be heard stop using the hoist controller immediately Attention Before starting to work on el...