Beta Draft Confidential
Installing and Wiring the Thermostat
Proliphix Thermostat Installation Guide, Release 1.0
11
Part No. 600-01000-100
Figure 5 Thermostat Jumper Locations
Prior to mounting the thermostat into the base plate, verify that the jumpers on the
thermostat are configured for your application (see
Table 5
).
To mount the thermostat into the base plate
:
1
Mount the thermostat into the base plate (see
page 3
) by inserting the top two hinges
into the corresponding receptacle holes in the top of the base plate.
2
Snap the bottom of the thermostat securely into the base plate.
Verifying the Thermostat’s Operating Status
This section describes the procedures you can use to verify that the heat, cool, and fan
controls are operating properly on your thermostat. Before you begin, verify that the
HVAC system’s power is set to “
On
” and press
HVAC
on the thermostat panel.
Testing the Heat Controls
1
Press
HVAC
.
2
Press
Mode
. A menu list appears.
3
Use the
Up
and
Down
arrows on the right side of the panel to select
Heat
.
4
Press
Select
.
5
Press
Back
.
6
Continuously press the
Up
arrow until the heat set point is higher than the temperature
reading. The heat relay should click and the HVAC system should activate the heat.
J3