21
Advance Setting Menu Page
There are three sub-menus under “Advance
User” setting: ELECTRIC, BATT and OTHERS.
ELECTRIC
Electric Setting Page 1
Output VOL.: Select the output rated voltage.
If the UPS is HV system, there are four options, 208V, 220V, 230V and 240V.
If the UPS is LV system, there are two options, 120V and 127V.
Output Frequency. Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “OP Freq.”. The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the
default setting.
Bypass Forbid:
Enable: Bypass forbid is allowed. When selected, it’s not allowed for running in Bypass mode
under any situations.
Disable: Bypass forbid is not allowed. When selected, UPS will run in Bypass mode depending on
“Bypass at UPS off” setting. It is the default setting.