Produal 6001TRC-P Manual Download Page 8

Produal Oy

Copyright © 2020 Produal Oy - All rights reserved - 07/2020 

PS 

6001TRC-P

  - 8/34

Web-site: 

www.produal.com

Enquiries: T:

 +358 10 219 9100   

E:

 [email protected]

Temperature Control Loop 
Operation 

The controllers can have up to two heating stages and cooling stages (as default one heating stage 
and one cooling stage), and can also carry out automatic change-over from heating to cooling via 
digital input / temperature measurement / network.

This allows various control configurations:-

One/Two Stage Heating Control

One/Two Stage Cooling Control

One/Two Stage Heating and One/Two Stage Cooling Control (up to three outputs)

One Stage Heating/Cooling Control (Change-Over)

The controller modulates the heating and cooling demand outputs according to the calculated setpoint  
and the current temperature. The control can be either P-control or PI-control. The calculated setpoint 
consists sum of Nominal Setpoint (nSP) and the user setpoint adjustment (SPA). 

As default for TRC-3A/2A2R, heating stage 1 output is linked to Y2 for modulating 0..10Vdc control, 
cooling stage 1 is linked to analogue output Y3. With TRC-1A2T/H-3R2T, heating stage 1 is linked to 
DO1 PWM control and cooling stage 1 is linked to DO2 PWM control. 

It is possible to set the control loop outputs to direct/reverse, which reverses the control output (valve) 
running direction (valve drives from 100% to 0%). This can be configured individually for each stage in 
the Configuration Parameters.

CONTROL

 OUTPUT

HEATING

STAGE 1

COOLING

STAGE 1

calcSP

TRC-P-3A/2A3R/1A2T

 - 0..10Vdc

TRC-P-1A2T

 - PWM

TRC-P-3A/2A3R/1A2T

 - 0..10Vdc

TRC-P-1A2T

 - PWM

HDz

MEASURED 
TEMPERATURE

100%

0%

+

-

COOLING

STAGE 2

TRC-P-3A/2A3R/1A2T

 - 0..10Vdc

HEATING

STAGE 2

NOTE: TRC-3A has maximum of 3 x 0-10Vdc outputs
NOTE: TRC-2A3R has maximum of 2 x 0-10Vdc outputs
NOTE: TRC-1A2T has maximum of 2 x PWM 24V outputs and 1 x 0-10Vdc outputs.

ECO Deadzone

fSP

2°C /

3.6°F

fSP = Frost Setpoint

TRC-P-3A/2A3R/1A2T

 - 0..10Vdc

HDz = COMFORT Heating Deadzone

CDz

CDz = COMFORT Cooling Deadzone

eHDz

eCDz

calcSP = Calculated Setpoint

Between heating and cooling stage 1 is a ’deadzone’. With P-control in the ’deadzone’ the cooling and 
heating loop demand is 0%. With PI-control, if the temperature remains in the ’deadzone’ for a 
prolonged period, the heating/cooling demand ramps to 0%. The ’deadzone’ allows the temperature to 
fluctuate around the setpoint without heating or cooling valves starting to open. The TRC has a built-in 
lock that prevents cooling and heating demands to be on simultaneously. 

The ’deadzone’ has an individual settings (HDz and CDz) for both heating and cooling side allowing 
asymmetrical setting. E.g. in some cases it is important that the cooling starts to respond faster than 
heating when the temperature deviates away from the setpoint.

Note: Conceptually calcSP - HDz is effective Heating Setpoint and  CDz is Effective Cooling 
Setpoint. For the user it is easier to set and display a single setpoint and the ’deadzone’ limits are set 
during the commissioning to provide effective heating and cooling setpoints..

The target temperature is typically adjusted by the user by pressing UP & DOWN buttons. The target 
temperature/deadzone is changed in different operating situations as follows; 

COMFORT MODE; target temperature as adjusted by the user (or via the networked system) 
and displayed on the screen. The calculated target setpoint (calcSP) consist of the Nominal Set-
point plus the user adjustment (SPA) set via the screen. The user setpoint adjustment is limited 
by the Setpoint Adjust Max/Min settings (as d/-3°).

ECO MODE; target Nominal Setpoint remains the same.The user adjustment (SPA) is disabled 
and the ’deadzone’ settings are expanded to Night Heating Deadzone and Night Cooling Dead-
zone.

OFF MODE; the device controls to Frost Setpoint (fSP). The user adjustment (SPA) is disabled.

NOTE:If activated, the High/low Limit Control shifts the effective target temperature (calculated 
setpoint) as required.

Heating / Cooling 
Change-Over

The main temperature control loop heating stage 1 and cooling stage 1 can be forced to operate in 
heating or cooling mode using the change-over function. The change-over is carried out using digital 
input, temperature measurement or over the network. This allows the same pipe works to be used for 
both heating and cooling in different seasons.

The change-over function is activated if it is selected for the DI1.RI1/RI2.

With digital input the change-over is activated when the input is activated. Over the network the 
change-over can be activated by setting the change-over parameter on.

Summary of Contents for 6001TRC-P

Page 1: ...sh Mounting in the US UK or EURO Wall Mounting Box Built In Temperature Sensor up to 2 x Remote NTC10 Sensors Wide Range of Input and Output Configurations Digital Input for Overrides Control of up to...

Page 2: ...nge 0 5000ppm CO2 Accuracy 50ppm 3 of the reading 25 C 77 F Technology Auto Calibrating Patented Non Dispersive Infrared NDIR Non Linearity 1 FS Warm Up Time 20 seconds Response Time 2 minutes Humidit...

Page 3: ...4 5mm Weight 220g CONN DESCRIPTION Y1 0 10Vdc Analogue Output 1 default fan speed Y2 0 10Vdc Analogue Output 2 default heating stage 1 Y3 0 10Vdc Analogue Output 3 default cooling stage 1 24V 24Vac dc...

Page 4: ...RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS...

Page 5: ...On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac 1A Triac...

Page 6: ...s based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz Deadzone ENERG...

Page 7: ...mmed to the stand by level Pressing the DIM icon when the device is in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings...

Page 8: ...emand is 0 With PI control if the temperature remains in the deadzone for a prolonged period the heating cooling demand ramps to 0 The deadzone allows the temperature to fluctuate around the setpoint...

Page 9: ...e formula Setpoint_Reset Limit_Setpoint Temperature Limit_Ratio NOTE The target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effec...

Page 10: ...A 2 A 3 R 1 A 2 T 0 1 0 V d c T R C P 1 A 2 T P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching...

Page 11: ...oint regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period in order t...

Page 12: ...ATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY CONT...

Page 13: ...Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0 100 Cleaning Mode After entering FURTHER INFORMATION screen by selecting the CLEANING ico...

Page 14: ...re not instantaneous Therefore they are not suitable for fast switching transition will be missed during the inherent delay time Note RI2 is not available with TRC P 2A3R 2 x 0 10Vdc Input AI Options...

Page 15: ...ge percentage The connected control loop output 0 100 is then scaled from minimum voltage to maximum voltage For example in the EC fan control if the fan is required to run always at minimum level the...

Page 16: ...e mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Analogue Output Scaling Anti JAM is not available in the 6 Port and 6 Port Reverse modes Number of Heating and...

Page 17: ...ault Digital Input Alarm Controller Status Information Display After entering CONFIGURATION PARAMETER GROUP screen and selecting the INFO icon it is possible to see the current status information of t...

Page 18: ...t 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Direction 0 Reverse Default 1 Direct Heating Stage 2 Dir Heating Stage 2 Direction 0 Reverse Default 1 Direct Cooling Stages Number of Cooling Stages 0...

Page 19: ...sabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Digital Inpu...

Page 20: ...Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period TRC P 1A2T TRC H 3R2T 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Default 1 2 Stop Bits...

Page 22: ...eter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode Override 0...

Page 23: ...Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Unsigned 16 0 2 0...

Page 24: ...verride Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Default 0 0 1...

Page 25: ...16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16 0 480 0...

Page 26: ...00 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns to 0 The blinds...

Page 27: ...2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching Time 3 Targ...

Page 28: ...2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16 0 2400 0...

Page 29: ...alogue Value Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humid...

Page 30: ...ies 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2 2 Stages...

Page 31: ...ng Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Network NTC10...

Page 32: ...igned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone 1 5 Zone...

Page 33: ...s Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192 Aux Lo...

Page 34: ...ual com Enquiries T 358 10 219 9100 E info produal fi NOTE Information is subject to change without prior notice Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112...

Reviews: