Produal Oy
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
PS
6001TRC-P
- 27/34
Web-site:
www.produal.com
Enquiries: T:
+358 10 219 9100
E:
188
Fan Off Delay - Only applicable if Min Fan Level
is set.
Unsigned 16
0..28,800
0..28,800seconds (Default 0)
0 = Infinite Delay
189
Aux Heating Loop Setpoint
Unsigned 16
0...950
0.0...95.0°C/°F
(Default 20°C)
190
Aux Heating Loop Proportional Band
Unsigned 16
10...500
1.0...50.0°C/°F
(Default 4°C)
191
Aux Heating Loop Integral Action Time
Unsigned 16
0..1200
0..1200 seconds (600s default)
192
Aux Loop Actuator Direction (actuator direction,
Direct = 0..100%, Reverse = 100..0%)
Unsigned 16
0..1
0 = Reverse Action (100-0%)
1 = Direct (0-100% Default)
200
Monday / Weekday Switching Time 1
Unsigned 16
0..2400
0..2400 (Default 0600)
201
Monday / Weekday Switching Time 2
Unsigned 16
0..2400
0..2400 (Default 1000)
202
Monday / Weekday Switching Time 3
Unsigned 16
0..2400
0..2400 (Default 1300)
203
Monday / Weekday Switching Time 4
Unsigned 16
0..2400
0..2400 (Default 1700)
204
Monday / Weekday Switching Time 5
Unsigned 16
0..2400
0..2400 (Default 2200)
205
Monday Switching Time 1 Target
Unsigned 16
0..3
0 = Comfort (Default)
1 = ECO
2 = Off
3 = Boost
206
Monday Switching Time 2 Target
Unsigned 16
0..3
207
Monday Switching Time 3 Target
Unsigned 16
0..3
208
Monday Switching Time 4 Target
Unsigned 16
0..3
209
Monday Switching Time 5 Target
Unsigned 16
0..3
210
Tuesday / Weekend Switching Time 1
Unsigned 16
0..2400
0..2400 (Default 0600)
211
Tuesday / Weekend Switching Time 2
Unsigned 16
0..2400
0..2400 (Default 1000)
212
Tuesday / Weekend Switching Time 3
Unsigned 16
0..2400
0..2400 (Default 1300)
213
Tuesday / Weekend Switching Time 4
Unsigned 16
0..2400
0..2400 (Default 1700)
214
Tuesday / Weekend Switching Time 5
Unsigned 16
0..2400
0..2400 (Default 2200)
215
Tuesday Switching Time 1 Target
Unsigned 16
0..3
0 = Comfort (Default)
1 = ECO
2 = Off
3 = Boost
216
Tuesday Switching Time 2 Target
Unsigned 16
0..3
217
Tuesday Switching Time 3 Target
Unsigned 16
0..3
218
Tuesday Switching Time 4 Target
Unsigned 16
0..3
219
Tuesday Switching Time 5 Target
Unsigned 16
0..3
220
Wednesday Switching Time 1
Unsigned 16
0..2400
0..2400 (Default 0600)
221
Wednesday Switching Time 2
Unsigned 16
0..2400
0..2400 (Default 1000)
222
Wednesday Switching Time 3
Unsigned 16
0..2400
0..2400 (Default 1300)
223
Wednesday Switching Time 4
Unsigned 16
0..2400
0..2400 (Default 1700)
224
Wednesday Switching Time 5
Unsigned 16
0..2400
0..2400 (Default 2200)
225
Wednesday Switching Time 1 Target
Unsigned 16
0..3
0 = Comfort (Default)
1 = ECO
2 = Off
3 = Boost
226
Wednesday Switching Time 2 Target
Unsigned 16
0..3
227
Wednesday Switching Time 3 Target
Unsigned 16
0..3
228
Wednesday Switching Time 4 Target
Unsigned 16
0..3
229
Wednesday Switching Time 5 Target
Unsigned 16
0..3
230
Thursday Switching Time 1
Unsigned 16
0..2400
0..2400 (Default 0600)
231
Thursday Switching Time 2
Unsigned 16
0..2400
0..2400 (Default 1000)
232
Thursday Switching Time 3
Unsigned 16
0..2400
0..2400 (Default 1300)
233
Thursday Switching Time 4
Unsigned 16
0..2400
0..2400 (Default 1700)
234
Thursday Switching Time 5
Unsigned 16
0..2400
0..2400 (Default 2200)
235
Thursday Switching Time 1 Target
Unsigned 16
0..3
0 = Comfort (Default)
1 = ECO
2 = Off
3 = Boost
236
Thursday Switching Time 2 Target
Unsigned 16
0..3
237
Thursday Switching Time 3 Target
Unsigned 16
0..3
238
Thursday Switching Time 4 Target
Unsigned 16
0..3
239
Thursday Switching Time 5 Target
Unsigned 16
0..3
240
Friday Switching Time 1
Unsigned 16
0..2400
0..2400 (Default 0600)
241
Friday Switching Time 2
Unsigned 16
0..2400
0..2400 (Default 1000)
242
Friday Switching Time 3
Unsigned 16
0..2400
0..2400 (Default 1300)
Register
Parameter Description
Data Type
Raw Data
Range