TRC-P Series User Interface

The figures below illustrate some of the TRC-P controller user displays. The multi-colour LCD screen 
is touch sensitive, easy to adjust and illustrates clearly the plant status information.

HEATING DEMAND

Room

20

.1

°C

STATUS INFORMATION 
BANNER

INTENSITY OF THE RED ON 
THE ENERGY RING 
CHANGES DEPENDING ON 
DIFFERENCE BETWEEN 
EFFECTIVE TARGET AND 
ROOM TEMPERATURES, AT 
2°C/3.6°F FULL RED

COOLING DEMAND

Target

21

.5

°C

PRESS DIM BUTTON TO 
SWITCH BACKLIGHT OFF

TARGET SETPOINT 
ADJUSTMENT BUTTONS

Outside

10

.5

°C

Humidity

45

%

Humidity

45

%

CO2

700

ppm

TRANSITIONS BETWEEN
ROOM, HUMIDITY, CO2, 
OUTSIDE (NETWORK)

FAN STATUS AND 
MANUAL CONTROL 
(FAN ROTATES 
WHEN RUNNING)

Target

21

.5

°C

A

A

OK

CO2 AMBER 
ALARM

CO2

700

ppm

CO2 ALARM DISPLAYS

CO2 RED ALARM

CO2

950

ppm

CO2

1300

ppm

SMALL ACTION 
CIRCLE

INDICATES 
CURRENT MODE - 
BUTTON FOR 
MODE SCREEN 
ACCESS

OFF (AWAY) MODE -
BUTTON TO MODE 
SELECTIO SCREEN

Wed 12:43

Wed 12:43

WHEN ENTERING THE MODE 
SCREEN THE CURRENT MODE 
STATUS IS DISPLAYED.

BY SELECTING THE NEW MODE 
THE DEVICE AUTOMATICALLY 
RETURNS TO THE HOME 
SCREEN (OR AFTER TIMEOUT).

MODE SCREEN

The colour of the ’Energy Ring’ indicates the heating/cooling demand. The ’Energy Ring’ is white at 
’deadzone’. The density of red/blue on the ’Energy Ring’ modulates based on how far from the 
Effective Heating/Cooling Setpoint the temperature is. When the difference is 2°C/3.6°F the ’Energy 
Ring’ is at full density

calcSP

HDz

MEASURED 
TEMPERATURE

+

-

CDz

Deadzone

ENERGY RING COLOURS

HDz - 2°/ 3.6°F

CDz + 2° / 3.6°F

.

Touchscreen

The TRC-P controller home screen has a number touch sensitive areas that allow the device settings 
to be changed.

UP and DOWN arrows; to alter the current control target setpoint temperature

SCREEN DIM ICON; dims the screen backlight/ switches backlight off

SMALL ACTION CIRCLE (that contains current room and/or floor temperature, CO2, humidity 
etc); allows access to FURTHER SETTINGS AND INFORMATION screen; password protected

FAN SPEED ICON; when FAN display is enabled, the fan ICON can be used to control the fan 
speed

COMFORT/ECO/OFF/BOOST ICON; used to select between COMFORT/ECO/OFF/BOOST 
modes. When selected, the MODE SELECTION screen is displayed and can be used to select 
the mode.

Programming Times and 
Targets

The TRC-P controllers have up to five programmable time switching times that can be configured to 
switch between COMFORT / ECO / OFF / BOOST modes. The times and targets can be set for 
individual weekdays or the thermostat can be switched 5+2 mode where the targets are set for 
WEEKDAYS or WEEKENDS.

The SCHEDULE OVERVIEW screen shows the current switching targets. By selecting the day it is 
possible to adjust the switching times and targets of the device.

NOTE: Switching from the 7 DAYS mode to 5+2 DAYS mode will set all weekday/weekend to the 
group settings. When returning back to 7 DAYS mode the setting are required to be re-entered for 
each day. 

Summary of Contents for 6001TRC-P

Page 1: ...sh Mounting in the US UK or EURO Wall Mounting Box Built In Temperature Sensor up to 2 x Remote NTC10 Sensors Wide Range of Input and Output Configurations Digital Input for Overrides Control of up to...

Page 2: ...nge 0 5000ppm CO2 Accuracy 50ppm 3 of the reading 25 C 77 F Technology Auto Calibrating Patented Non Dispersive Infrared NDIR Non Linearity 1 FS Warm Up Time 20 seconds Response Time 2 minutes Humidit...

Page 3: ...4 5mm Weight 220g CONN DESCRIPTION Y1 0 10Vdc Analogue Output 1 default fan speed Y2 0 10Vdc Analogue Output 2 default heating stage 1 Y3 0 10Vdc Analogue Output 3 default cooling stage 1 24V 24Vac dc...

Page 4: ...RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS...

Page 5: ...On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac 1A Triac...

Page 6: ...s based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz Deadzone ENERG...

Page 7: ...mmed to the stand by level Pressing the DIM icon when the device is in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings...

Page 8: ...emand is 0 With PI control if the temperature remains in the deadzone for a prolonged period the heating cooling demand ramps to 0 The deadzone allows the temperature to fluctuate around the setpoint...

Page 9: ...e formula Setpoint_Reset Limit_Setpoint Temperature Limit_Ratio NOTE The target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effec...

Page 10: ...A 2 A 3 R 1 A 2 T 0 1 0 V d c T R C P 1 A 2 T P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching...

Page 11: ...oint regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period in order t...

Page 12: ...ATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY CONT...

Page 13: ...Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0 100 Cleaning Mode After entering FURTHER INFORMATION screen by selecting the CLEANING ico...

Page 14: ...re not instantaneous Therefore they are not suitable for fast switching transition will be missed during the inherent delay time Note RI2 is not available with TRC P 2A3R 2 x 0 10Vdc Input AI Options...

Page 15: ...ge percentage The connected control loop output 0 100 is then scaled from minimum voltage to maximum voltage For example in the EC fan control if the fan is required to run always at minimum level the...

Page 16: ...e mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Analogue Output Scaling Anti JAM is not available in the 6 Port and 6 Port Reverse modes Number of Heating and...

Page 17: ...ault Digital Input Alarm Controller Status Information Display After entering CONFIGURATION PARAMETER GROUP screen and selecting the INFO icon it is possible to see the current status information of t...

Page 18: ...t 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Direction 0 Reverse Default 1 Direct Heating Stage 2 Dir Heating Stage 2 Direction 0 Reverse Default 1 Direct Cooling Stages Number of Cooling Stages 0...

Page 19: ...sabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Digital Inpu...

Page 20: ...Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period TRC P 1A2T TRC H 3R2T 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Default 1 2 Stop Bits...

Page 22: ...eter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode Override 0...

Page 23: ...Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Unsigned 16 0 2 0...

Page 24: ...verride Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Default 0 0 1...

Page 25: ...16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16 0 480 0...

Page 26: ...00 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns to 0 The blinds...

Page 27: ...2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching Time 3 Targ...

Page 28: ...2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16 0 2400 0...

Page 29: ...alogue Value Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humid...

Page 30: ...ies 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2 2 Stages...

Page 31: ...ng Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Network NTC10...

Page 32: ...igned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone 1 5 Zone...

Page 33: ...s Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192 Aux Lo...