INPUTS & OUTPUTS
Parameter Name
Description
Range
Room Sensor Text
Description for the Room Sensor (Built-In Sensor /
RI1/RI2)
1 = Room (Default)
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
Floor Sensor Text
Description for the Floor Sensor (RI1/RI2)
Default; 2 = Floor
Note: Disabled removes Floor Sensor Text and
Measurement from Display. The device may require
Soft Reset after setting ’Disabled’. This is done by
entering and exiting the System configuration menu.
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
Aux. Sensor Text
Description for the Aux Sensor (RI1 / RI2 / Network
Value)
Default; 3 = Outside
Note: Disabled removes Aux Sensor Text and
Measurement from Display. The device may require
Soft Reset after setting ’Disabled’. This is done by
entering and exiting the System configuration menu.
Humidity Display
Enable / Disable Humidity Display (if option fitted)
0 = Disabled
1 = Enabled (default)
Digital Input Mode
Digital Input Operation
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Heating/Cooling Change-Over
5 = Disable Cooling
6 = Contact Alarm
7 = Network Measurement
8 = Close for BOOST
9 = Open for BOOST
Digital Input Delay
Digital Input Delay Timer (transition from active to
non-active)
0..28,800 seconds (Default 0s)
RI1 Mode
Resistive Input 1 Mode
0 = Disabled (default)
1 = Room (NTC10 Temp Control)
2 = Floor (NTC10 Floor Low/High
Limit Control)
3 = Aux. Loop
4 = Network NTC10
5 = Network 0-10V
6 = CO2; 0..2000ppm = 0-10V
(AI-option)
7 = Main Loop (Control Temp;
0..50°C = 0-10V; AI-option)
8 = Close for ECO (DI-mode)
9 = Open for ECO (DI-mode)
10 = Close for OFF (DI-mode)
11 = Open for OFF (DI-mode)
RI2 Mode
Resistive Input 2 Mode
Aux. Loop Source
Source for the Auxiliary Loop Sensor (Display
activated when valid temperature is sent)
0 = Built-In Sensor
1 = Network Temp
Internal Sensor Cal.
Internal Sensor One Point Compensation
-10.0..+10.0 °C/°F
RI1 Cal.
Sensor Connected to RI1 Calibration
-10.0..+10.0 °C/°F
RI2 Cal.
Sensor Connected to RI1 Calibration
-10.0..+10.0 °C/°F
CO2 Cal.
CO2 Sensor Calibration (CO2 Models)
-500...+500 ppm